oF
on - oF - Lb
Defrost display Lock
oF= display free
on= Lock on
temperature Pr1 before
defrost
Lb= Lock on label “dF”
(during defrosting) and
“Pd” (during
post-defrosting)
dL
32
oF
oF - on
Defrost at power on
Sd
31
oF
oF ÷ 99
min
Compressor delay after
defrost (drainage time)
td
30
rt
rt - ct - cS
Defrosting intervals
Counting mode:
rt = real time
ct = On ot time
cS = defrost every off ot
dC
29
2.0
- 58 ÷ 99
°C/°F
Defrost enable
temperature
tS
28
8.0
- 58 ÷ 99
°C/°F
Defrost stop
temperature
tE
27
30
0 ÷ 99
min
Max. lenght of defrost
cycle
dE
26
6
oF ÷ 99
hrs.
Defrosting interval
di
25
Group -Fn
(parameters relative to evaporator fan control)
oF
oF ÷ 99
min
Fan delay after defrost
Fd
38
1.0
0 ÷ 30
°C/°F
Differential fan control
dF
37
-58
- 58 ÷ 99
°C/°F
Low temperature fan off
LF
36
10.0
- 58 ÷ 99
°C/°F
High temperature fan
off
FL
35
oF
on - oF
Fan status during
defrost
FE
34
on
on - oF
Fan status with
compressor off
FC
33
Note
Def.
Range
Description
Par.
Group -Pr
(parameters relative to compressor protection and
power on delay)
0
-30 ÷ 30
V
Voltage calibration
OU
45
oF
oF ÷ 99
sec.
Voltage alarms delay
Ud
44
oF
oF/ 9 ÷ 27
V x 10
High voltage alarm
HU
43
oF
oF/ 9 ÷ 27
V x 10
Low voltage alarm
LU
42
oF
oF ÷ 99
min
Delay at power on
od
41
oF
oF ÷ 99
min
Compressor protection
time
Pt
40
1
1 - 2 - 3
Type of compressor
protection:
1= delay at switch on
2= delay after switch off
3= delay between starts
PS
39
Note
Def.
Range
Description
Par.
Group -AL
(parameters relative to alarms)
1.0
0 ÷ 30
°C/°F
Temperature Alarms
Differential
Ad
49
oF
oF / - 58 ÷ 99
°C/°F
Low temperature Alarm
threshold
LA
48
oF
oF / - 58 ÷ 99
°C/°F
High temperature Alarm
threshold
HA
47
Ab
Ab - dE
Temperature alarms
Type:
Ab = Absolute
dE =Relative to Set
Ay
46
Note
Def.
Range
Description
Par.
3
oF ÷ 99
min
Alarm delay with open
door
oA
54
oF
oF ÷ 99
hrs
Temperature alarms
delay after continuous
cycle
cA
53
60
oF ÷ 99
min
Temperature Alarms
delay and unlock
display delay after
defrost
dA
52
2
oF ÷ 99
hrs
Temperature Alarms
delay at power on
PA
51
oF
oF ÷ 99
min
Temperature Alarms
delay
At
50
Group -ot
(parameters relative to configuration of outputs)
oF
oF ÷ 99
min
Time relative to auxil-
iary output
tu
61
0
oF / 1 / 2 / 3
Function mode auxiliary
output:
oF= No Function
1= control output
delayed
2= manual activation by
key or digital input.
3= Light
FO
60
3
oF / 1 / 2 / 3
Buzzer function mode
oF = disable
1 = active alarms only
2 = key pressed only
3 = active alarms and
key pressed
bu
59
Au
oF/Ot/dF/
Fn/Au/At/
AL/An/ -At/
-AL/ -An
Configuration of output
function OUT4:
see “o1”
o4
58
Fn
oF/Ot/dF/
Fn/Au/At/
AL/An/ -At/
-AL/ -An
Configuration of output
function OUT3:
see “o1”
o3
57
dF
oF/Ot/dF/
Fn/Au/At/
AL/An/ -At/
-AL/ -An
Configuration of output
function OUT2:
see “o1”
o2
56
Ot
oF/Ot/dF/
Fn/Au/At/
AL/An/ -At/
-AL/ -An
Configuration of output
function OUT1:
oF= No function
Ot= Temperature
control (compressor)
dF= defrosting
Fn= fans
AS= Auxiliary
At= Silenceable alarm
AL= Alarm not
silenceable
An= memorised alarm
o1
55
Note
Def.
Range
Description
Par.
Group -Pn
(parameters relative to configuration of the keyboard)
oF
oF ÷ 99
Access Password to
parameter functions
PP
65
oF
oF ÷ 30
min
Keyboard lock function
delay
Lo
64
oF
oF / 1 / 2 / 3
Function mode key U:
see “UF”
Fb
63
oF
oF / 1 / 2 / 3
Function mode key U:
OFF= No function
1= Auxiliary output
command
2= Continuous cycle
command
3= Selection of active
Set Point
4= Switch on/Switch off
(Stand-by)
UF
62
Note
Def.
Range
Description
Par.
ASCON TECNOLOGIC - TLB55
- OPERATING INSTRUCTIONS - Vr. 04 - 02/12 - ISTR-MTLB55ENG04 - PAG. 9