Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0
PAG. 21
Range:
00.00 to... 11.11 where:
0 =
Event OFF;
1 =
Event ON.
Note:
For more details see [100]Pr.E1 parameter.
[111] Pr.S4 - Set point of the fourth soak
Available:
When [92] Pr.F is different from nonE, [101]
Pr.S2 is different from oFF and [106] Pr.S3 is
different from OFF.
Range:
From [76] SPLL to [77] SPHL;
oFF = Program end.
Note:
For more details see [101]Pr.S2 parameter.
[112] Pr.G4 - Gradient of the fourth ramp
Available:
When [92] Pr.F is different from nonE, [101] Pr.S2
is different from oFF, [106] Pr.S3 is different from
OFF and [111] Pr.S4 is different from OFF.
Range:
0.1... 999.9 enginering units per minute;
inF =
Step transfer.
[113] Pr.t4 - Time of the fourth soak
Available:
When [92] Pr.F is different from nonE, [101] Pr.S2
is different from oFF, [106] Pr.S3 is different from
OFF and [111] Pr.S4 is different from OFF.
Range:
0.00... 99.59 time units.
[114] Pr.b4 - Wait band of the fourth soak
Available:
When [92] Pr.F is different from nonE, [101] Pr.S2
is different from oFF, [106] Pr.S3 is different from
OFF and [111] Pr.S4 is different from OFF.
Range:
From OFF to 9999 engineering units.
Note:
For more details see [99] Pr.b1 parameter.
[115] Pr.E4 - Event of the fourth segment
Available:
When [92] Pr.F is different from nonE, [101] Pr.S2
is different from oFF, [106] Pr.S3 is different from
OFF and [111] Pr.S4 is different from OFF.
Range:
00.00... 11.11 where:
0 =
Event OFF;
1 =
Event ON.
Note:
For more details see [100]Pr.E1 parameter.
[116] Pr.St - Program status
Available:
When [92] Pr.F is different from nonE.
Range:
run =
Program Run;
HoLd = Program Hold;
rES =
Program reset.
Note:
This parameter allows to manage program execution
by a parameter.
]
PAn group - Operator hMI
[117] PAS2 - Level 2 password: Limited access level
Available:
Always.
Range:
oFF = Level 2 not protected by password
(as level 1 = Operator level);
1... 200.
[118] PAS3 - Level 3 password: Complete
configuration level
Available:
Always.
Range:
3... 200.
Note:
Setting [117] PAS2 equal to [118] PAS3, the level 2
will be masked.
[119] PAS4 - Level 4 password:
CODE configuration level
Available:
Always
Range:
201... 400.
[120] uSrb -
button function during RUN TIME
Available:
Always.
Range:
nonE = No function;
tunE = Auto-tune/self-tune enabling.
A single press (longer than 1) starts the
auto-tune.
oPLo = Manual mode.
The first pressure puts the instrument in
manual mode (OPLO) while a second one
puts the instrument in Auto mode.
AAc = Alarm reset.
ASi =
Alarm acknowledge
chSP = Sequential set point selection (see note).
St.by = Stand by mode
The first press puts the instrument in stand
by mode while a second one puts the in-
strument in Auto mode.
Str.t = Timer run/hold/reset (see note).
P.run = Program run (see note).
P.rES = Program reset (see note).
P.r.H.r = Program run/hold/reset (see note).
Notes: 1.
When “Sequential set point selection” is used,
every press of the
button (longer than 1
second) increase the value of A.SP (active set
point) of one step.
The selection is cyclic: SP -> SP2 -> SP3 -> SP4
When a new set point is selected using the
key, the display will show for 2 seconds the
acronym of the new set point (e.g. SP2).
2.
When “Sequential set point selection” is used, the
number of set points selectable is limited by [73] nSP.
3.
When “Timer run/hold/reset” is selected, a short
press starts/stops(hold) timer count while a long
press (longer than 10 seconds) resets the timer.
4.
When “Program run” is selected, the first press
starts the program execution but a second press
restarts the program execution from the beginning.
5.
When “Program reset” is selected, a short press
allows it to reset the program execution.
6.
When “Program run/hold/reset” is selected, a
short press starts/stop (Hold) program execution
while a long press (longer than 10 seconds)
resets the program.
[121] diSP - Display management
Available:
Always
Range:
nonE = Standard display
Pou = Power output
SPF = Final set point
Spo = Operative set point
AL1 = Alarm 1 threshold
AL2 = Alarm 2 threshold
AL3 = Alarm 3 threshold
Pr.tu = During a soak, the instrument will show the
elapsed time of the soak
•
During a ramp the display will show the ope-
rative set point.
•
At the end of the program execution, the