Ascon Tecnologic - KX Line - ENGINEERING MANUAL -Vr.4.0
PAG. 22
instrument will show “P.End” messages alter-
nately with the measured value.
•
When no program is running, the instrument
will show the standard display.
Pr.td = During a soak, the instrument will show the
remaining time of the soak (count down).
•
During a ramp the display will show the ope-
rative set point.
At the end of the program execution, the
instrument will show “P.End” messages alter-
nately with the measured value.
•
When no program is running, the instrument
will show the standard display.
P.t.tu = When the programmer is running, the
display will show the total elapsed time.
At the end of the program execution, the
instrument will show “t.End” messages
alternately with the measured value.
P.t.td = When the programmer is running, the
display will show the total remaining time
(count down).
At the end of the program execution, the
instrument will show “P.End” messages
alternately with the measured value.
ti.uP = When the timer is running, the display will
show the timer counting up.
At the end of the counting, the instrument
will show “t.End” messages alternately with
the measured value.
ti.du = When the timer is running, the display will
show the timer counting down.
At the end of the counting, the instrument
will show “t.End” messages alternately with
the measured value.
PErc = Percent of the power output used during soft
start (when the soft start time is equal to
infinite, the limit is ever active and it can be
used also when ON/OFF control is selected).
[122] di.CL - Display colour
Available:
Always.
Range:
0 =
The display colour is used to show the
actual deviation (PV - SP);
1 =
Display red (fix);
2 =
Display green (fix);
3 =
Display orange (fix).
[123] AdE - Deviation for display colour management
Available:
When [122] di.CL = 0.
Range:
1... 9999 engineering units.
[124] diS.t - Display time out
Available:
Always.
Range:
oFF = The display is always ON;
0.1... 99.59 minutes and seconds.
Note:
This function allows to turn OFF the display when no
alarm is present and no action is made on the instrument.
When diS.t is different from OFF and no button is
pressed for more than the programmed time out, the
display goes OFF and only 4 segments of the less
significant digit are turned ON in sequence in order to
show that the instrument is working correctly.
If an alarm occures or a buton is pressed, the display
will come back to the normal operation.
[125] FiLd - Filter on the displayed value
Available:
Always.
Range:
oFF = Filter disabled;
From 0.0 (oFF) to 20.0 engineering units.
Note:
This is a “window filter” related to the set point; it is
applied to the displayed value only and it have no
effect on the other functions of the instrument (control,
alarms, etc.).
[126] bG.F - Bargraph function (KX3 only)
Available:
Always.
Range:
nonE = Bargraph not lit;
Pou = Output power calculated by PID (single ac-
tion: 0... 100%, double action: -100... +100%);
Po.h = Energy Used (kWh);
Pr.tu = Elapsed time of the program in execution;
Pr.td = Time to end of the program in execution;
Pr.tS = Time to end of the program segment in
execution;
ti.uP = Elapsed time of timer (T1 and T2);
ti.du = Time to end of timer (T1 and T2);
r.iSP = Time to preventive maintenance.
Note:
Displaying values using the bar graph will be possible
only if the variables involved are configured.
If it has been chosen to display the time of the
program or time of the timer, the bargraph will be off if
the option is not configured, it will have the first LED lit
if the option is configured but not running.
[127] dSPu - Status of the instrument at power up
Available:
Always.
Range:
AS.Pr = Starts in the same way it was prior to the
power down;
Auto = Starts in Auto mode;
oP.0 = Starts in manual mode with a power output
equal to zero.
St.bY = Starts in stand-by mode
Notes: 1.
When you change the value of [128] oPr.E, the
instrument forces [129] oPEr parameter equal to
Auto.
2.
During program execution the instrument
memorize the segment currently in use and, by a
30 minutes interval, it memorize also the elapsed
time of the soaks.
If a power down occurs during program execution,
at the next power up the instrument is able to
continue the program execution starting from
the segment in progress at power down and, if
the segment was a soak, it is also capable to
restart from the soak time minus the elapsed time
memorized.
In order to obtain this features, the “[127] dSPu -
Status of the instrument at power up” parameter
must be set to “AS.Pr”.
If the “[127] dSPu” parameter is different from
“AS.Pr” The memorization function is inhibited.
[128] oPr.E - Operative modes enabling
Available:
Always.
Range:
ALL = All modes will be selectable by the next
parameter.
Au.oP = Auto and manual (OPLO) mode only will be
selectable by the next parameter.