GENERAL NOTES
GENERAL NOTES
5.3. SHELVES (HEIGHT ADJUSTABLE)
2
3
4
5
6
7
8
9
Load capacities
IO90.195.060.K1.WDC
O90.195.120.K1.WDC / IO90.195.120.K2.WDC*
max.
25 kg
max.
75 kg
max.
50 kg
Only with
Special interior equipment:
Order No. 38516
Order No. 38517
Order No. 38518
Order No. 38519
*ATTENTION:
Model IO90.195.120.K2.WDC:
The positions of the fire suppression device, smoke detector and thermal
sensor must not be changed when changing the height of the grid shelves.
6. STORAGE
ATTENTION:
Never store obviously damaged lithium-ion batteries inside buildings. Dispose of them without delay in
disposal containers that are provided outside the building and approved for transport.
6.1. NOTES ON STORAGE AND CHARGING
Storage
It is recommended to store new and used lithium-ion batteries separately (each on a different storage level)
in the safety storage cabinet.
Occupation of the storage levels
Grid shelves may be covered only up to 60% by battery chargers and batteries in order to ensure trouble-free
operation of the fire suppression system and sufficient air circulation
ATTENTION:
It is not permitted to occupy the complete area of the grid shelves
IO90.195.120.K2.WDC:
The following substances may not be stored in the cabinets with a fire suppression system:
acids, alkalis,
magnesium, other metals (in powder form).
ATTENTION:
In the area in front of the fire suppression unit there is a
distance of at least 150 mm to be observed.
Li-Ion Li-Ion
150 mm
7. VENTILATION
CAUTION
The fire protection valves near the supply and extraction air connections are safety and
maintenance-relevant components.
In order to check the correct function or to replace a defective element, please note that when connecting
to an exhaust air system, flexible connection hoses or sliding pieces are used to ensure easy removal and
reassembly of the exhaust air connection.
Ventilation wheel for technical ventilation
The ventilation wheel serves as an indicator for correct ventilation.
If the wheel turns, the necessary 10-fold air recirculation rate is exceeded.
8. BATTERY FIRE • FIRE • DISPOSAL
CAUTION
Following a battery fire and the triggering of the fire suppression system, the safety storage cabinet must
be subjected to a thorough inspection so that both fire protection and CE conformity are retained. For this
purpose the cabinet must be handed over to asecos GmbH‘s main factory in Gründau, where the specialist
department – depending on the extent of the damage – will appraise the economic viability and technical
possibilities of a repair. The customer then receives a quotation either for a repair or for an exchange, which
can be forwarded to the responsible insurance company.
8.1. FIRE INSIDE THE CABINET (BATTERY FIRE)
• For fast transport the cabinets are equipped with a transport base.
• The cabinets are automatically disconnected from the mains supply in the case of transport.
ATTENTION:
Prior to transport the doors must be locked and the extraction unit removed from the cabinet!
Transport may only be carried out by technical personnel!