14
15
SPECIFIC NOTES: BATTERY STORE PRO
SPECIFIC NOTES: BATTERY STORE PRO
10. IO90.195.120.K2.WDC
10.1. CONNECTION TO THE POWER SUPPLY
LED: Operating (green)
RESET BUTTON
LED: Error (red)
Connections on the headpiece:
1
2
Mains plug connector
Potential-free switch
contact
Connection to the
power supply
1
2
230 V
3
Connection to the power
supply with 400 V
(optional with item
HF.E.32822)
1
2
400 V
3
CAUTION:
Subsequent retrofitting is possible using the plug connection, so that no intervention in the electrical
components is required.
10.2. SELF TEST
Starts 5 seconds after
connection to the
mains supply
1
2
3
4
5
6a
10.3. ERROR DURING SELF-TEST
1
2
5
3
5
sec
4
5
ATTENTION:
After pressing the reset button, the self-test begins again. If the error persists, please contact the asecos
Service Dept.
10.4. ERROR AND ALARM OVERVIEW
EVENT
LED GREEN
LED RED
ACOUSTIC ALARM
ACTIONS
Error during self-test off
on
5 signal tones
1.) Restart with RESET button
If error persists:
2.) Contact Service
Service interval
reached
flashing
off
off
Contact Service
Power failure
Flashes every
20 seconds
off
3 short signal tones
every 60 seconds
Check power supply
Warning message:
Temperature in the
cabinet >50 °C
off
on
long tone interval
(every 2 seconds for
250 ms)
see 10.7
Alarm stage 1:
Smoke detector
detects smoke in the
cabinet
off
on
medium tone interval
(every 0.5 seconds for
250 ms)
see 10.8
Alarm stage 2:
Smoke detector
detects smoke in the
cabinet, Tempera-
ture in the cabinet
>70 °C
off
flashing
short tone interval
(every 0.25 seconds for
125 ms)
see 10.9