SPECIFIC NOTES: BATTERY STORE PRO
SPECIFIC NOTES: BATTERY STORE PRO
10.5. POTENTIAL-FREE ALARM CONTACT
NOTE:
The potential-free alarm contact is for connecting a signal to a control room/control centre. A direct
connection to a fire alarm system is not recommended or may only be done in consultation with those
responsible for the system.
In general, however, the connection of the signal to a manned control room/control centre is
always recommended!
The connection of the potential-free switch contact must always be done by the customer (not a service
item).
(AC) / (DC)
(AC) / (DC)
Connector
Internal
alarm contact
Connection instructions
• Use only the supplied mating part (colour-coded black) to the plug for the connection
• The connection must be done by a qualified electrician
• The contact is designed for a max. DC voltage of 30 V or a max. AC voltage of 230 V
• The maximum current load is 10 A
• The switch contact is normally closed!
• The switch contact opens as soon as mains voltage is present and no error is pending (device is „ready to
operate“)
10.6. WARNING/FIRE SUPPRESSION SYSTEM
• The warning/fire suppression system offers the option of connection to a constantly manned building ma-
nagement system or fire alarm centre.
• Make use of this option so that trained rescue personnel can be quickly alerted and be on-site in a very short
time and, following an initial assessment of the situation, immediately initiate further measures (for example,
transporting the cabinet out of the building).
• The extinguishing agent, based on calcium carbonates, is harmless in the necessary extinguishing agent con-
centration and has no harmful effects on the human organism
• In case of triggering, the aerosol is ejected at a high temperature and temperatures of over 300 °C are briefly
generated in front of and on the housing of the fire suppression cartridge (according to the manufacturer‘s
data, a minimum distance to combustible materials need not be maintained; however, a distance of at least
150 mm to the fire suppression cartridge should generally be maintained)
• After triggering of the fire suppression cartridge, ventilate the room and the cabinet well, observing the instruc-
tions in point 8.
ATTENTION:
The complete warning/fire suppression system is active only with mains operation.
The integrated smoke detector is part of the entire fire suppression system (direct power supply)
10.7. WARNING MESSAGE
>50 °C
1
2
3
sofern
aufgeschaltet
4
Actions
• immediate visual inspection of the system
by the company‘s own qualified personnel
• initiation of necessary actions
• if the interior temperature falls below 50 °C, the system returns to normal operation and the visual and acoustic
signals are switched off
.
10.8. ALARM STAGE 1
!
1
2
3
sofern
aufgeschaltet
4
Actions
• immediate visual inspection of the system
by technical personnel (e.g. fire brigade)
• subsequently, initiation of necessary actions
• if the smoke detector does not detect any further smoke development in the cabinet, the system can be reset
to normal operation by briefly disconnecting the mains voltage