Asentria SiteBoss 420 User Manual
18
Alarm Actions
– sets the action(s) to be taken if Alarm State is set to ON, and the humidity exceeds any of the Very
High / High / Low / Very Low thresholds shown to the right. Alarm Actions are configured as
En
where
n
corresponds
to the Email Address index number on the Email Alerts tab, and
Tn
where
n
corresponds to the SNMP Manager index
number on the SNMP Alerts tab. Multiple actions are listed with no delimiters, so for example:
T1T2E2E3
would send
a trap to SNMP Managers 1 and 2, and an Email message to Email Addresses 2 and 3.
Deadband
– sets the range, in percentage, on either side of a humidity setting that prevents the event from repeatedly
going in and out of the "event state" as the actual humidity fluctuates above and below the humidity setting. Default
setting is 3%.
Very High / High / Low / Very Low Temp
– are the settings for each of four humidity thresholds that the S420 can
alarm on. If Alarm State is set to ON, and the humidity rises above the High and Very High settings, the Alarm Actions
will take effect. Same process if the humidity drops below either the Low or Very Low settings. Default settings are:
Very High (90), High (70), Low (30), Very Low (15).
Very High / High / Low / Very Low Severity
– displays a drop down menu of four descriptive words – Info, Minor,
Major, Critical – that allow you to assign a severity rating to this alarm. This word will appear in an SNMP Trap alert,
but does not appear in an Email alert. Default setting for all is “Info”.