Asentria SiteBoss 420 User Manual
Alerts
General Settings Tab
System Alert Actions
– sets the action(s) to be taken when the Power-Up Alert is triggered, if enabled. Eventually
there may be other types of “system alerts” for which these actions would also apply. System Alert Actions are
configured as
En
where
n
corresponds to the Email Address index number on the Email Alerts tab, and
Tn
where
n
corresponds to the SNMP Manager index number on the SNMP Alerts tab. Multiple actions are listed with no
delimiters, so for example:
T1T2E2E3
would send a trap to SNMP Managers 1 and 2, and an Email message to Email
Addresses 2 and 3.
Power-Up Alert
– is an On/Off toggle to enable an alert to be sent whenever the S420 goes from a powered-down to
a powered-up state. Default setting is Off.
Individual Alert Repeat Frequency
– sets the number of minutes (0 –65535) between repeat alert notifications. This
applies to ALL alerts for ALL enabled events. 0 means no repeat alert notifications are sent. Default setting is 0.
Send Return to Normal Alerts
– is an On/Off toggle to send an alert if an event returns to it’s "normal“ or "inactive“
state. The alert is sent via the same alert or alarm actions that are configured for the event itself. Default setting is
On.