Asentria SiteBoss 420 User Manual
28
Type2 EventSensor™ Setup
As of the publishing date for this User Manual:
a. only Temperature (ES-T) and Temperature/Humidity (ES-TH) Type2 EventSensors are available.
b. only three Type2 EventSensor’s are supported.
Connections
The 9-pin mini DIN cable end of the EventSensor cable plugs in to the SensorJack port on the back panel of the S420.
The RJ45 end of that cable plugs in to the Type2 EventSensor RJ45 port labeled Control. Additional Type2
EventSensors are chained together using Cat-5 straight-thru cable from the Sensor port on the first EventSensor, to
the Control port on the next EventSensor. Be sure to set the DIP switches for each additional EventSensor so that
each occupies it’s own slot as per the chart below.
DIP Switch Settings
Defines up to 16 address locations (however only Slots 1 thru 8 are currently available). The S420 currently supports
only three Type2 EventSensors, so set them for Slot 1, Slot 2 and Slot 3. Note that the DIP switch is numbered from
left to right, 1 through 4. The Most Significant Bit (MSB) is switch location 1.
1 = DIP Switch up 0 = DIP Switch down
DIP SW
Slot
DIP SW
Slot
DIP SW
Slot
DIP SW
Slot
0000
= 1
0100
= 5
1000
= 9
1100
= 13
0001
= 2
0101
= 6
1001
= 10
1101
= 14
0010
= 3
0110
= 7
1010
= 11
1110
= 15
0011
= 4
0111
= 8
1011
= 12
1111
= 16
Configuration
Refer to the
section for configuration instructions.