Actions List
Enter one or more actions using this format:
(For more details see the users manual)
----------------------------------------------
Cancel : cancel(idname)
Dialup Pager : dpage(index)
Dispatcher : dispatch(phone# or index)
Email : email(email or index)
Group : group(groupname)
ID : id(id name)
Inform : inform(ipaddress or index)
Malert : malert(phone# or index)
Modem : modem(phone# or index)
Postpone : postpone(idname, seconds)
Pause : pause(seconds)
Relay : relay(action, eventsensor, point)
SMS : sms(phone# or index)
Talert : talert(ipaddress or index)
Trap : trap(ipaddress or index)
(separate multiple actions using semicolon)
Current Actions:
Enter Data Alarm Actions:
The Actions List provides you with a flexible mechanism to tell the unit how to react to events. An action list is a
text string that specifies what the unit should do upon an event. It's comprised of a list of keywords and
parameters separated by semicolon. Each keyword specifies a certain action and has its own parameter set,
which is enclosed in parentheses. Refer to
in the Features chapter for more information.
EventSensor Device Settings
The S530 supports a wide variety of internal and external sensor devices and relays, including contact closures,
temperature and humidity sensors, analog voltage and current sensors, and relays. For the purposes of clarity,
all of these will be generally referred to as “EventSensors” (ES) unless a specific type of sensor or relay is being
described.
Internal sensors are those on Expansion Cards that can be installed in the expansion bays on the back of the
S530. External sensors are separate devices available from Asentria that are connected to serial I/O 1 (set to
ESBUS mode) via an RS232-RS485 ES Bus Adapter. Additionally, the two serial I/O ports on the S530 can also
be wired as contact closures.
The Sensor Events Menu is used to configure and control EventSensors. If you don't have any internal sensors or
relays, or remote ES modules connected, this menu will be unpopulated except for the two internal I/O ports
shown as “2-CC”. Because of the numerous ES configurations possible, menus shown in this section will
probably not look exactly like the ones for your S530. (The menu below shows an S530 Sensor Events Menu
with the two internal I/O ports and one external ES-3 module with temperature sensor and 8 contact closures.)
SiteBoss 530 - Sensor Events Menu
Name ID Alive Number Configuration
A) INTERNAL -------- - 200 2-CC
B) ES-3 Test 06021892 Y 1 1-TS 8-CC