Asentria SiteBoss 530 User Manual
44
No-Data n Alarm Settings
No Data Alarms can be configured on the S530 to monitor data coming in via the serial ports, and take an alarm
action if a certain period of time passes with no data.
SiteBoss 530 - No-Data Alarm 1 Settings
A) Alarm Enable [OFF]
B) Alarm Actions []
C) Alarm Message [No-Data Timeout 1]
D) Alarm Class [Info]
E) Trap Number [505]
F) Schedule 1 Begin Time [00:00]
G) Schedule 1 End Time [00:00]
H) Schedule 1 Duration (minutes) [0]
I) Schedule 2 Begin Time [00:00]
J) Schedule 2 End Time [00:00]
K) Schedule 2 Duration (minutes) [0]
L) Apply Alarm on Days [MTuWThF]
M) Enable Ports
N) Add Exclusion
O) Delete Exclusion
[]
[]
No-Data n Alarm Settings
allows you to configure two separate No-Data Alarms, each of which can be
configured for two different ranges of times with different time durations. The periods of time should be configured
to match the calling patterns of your business or organization. For example, if your normal business hours are M-
F 8:00 to 5:00, you may want to set lower time durations during those hours than you would “after hours” when
call volumes are lighter and the periods of time where there is "no data“ might be longer.
Alarm Enable
is an ON/OFF toggle to enable the no-data monitor. Default setting is OFF.
Alarm Actions
displays the Actions List, a menu where the action string for the event is configured. This field will
be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to
in the Features chapter for more information.
Alarm Message
sets the text string to be delivered with this event’s alarms. Default setting is "No-Data Timeout
n
“. (Max length 126 chars)
Alarm Class
sets the class for the alarm. When this option is selected, a list of the classes previously defined in
is displayed, from which you can select one to be assigned to this No-Data Alarm.
Trap Number
sets the number to be sent with any SNMP traps for this event. Default is 505, but trap number
can also be set in the range of 1000 – 1199 as needed.
Schedule n Begin Time / End Time
sets the beginning and ending times (24 hour clock) for each of two ranges
of time.
Schedule n Duration
is the number of minutes (0-65535) the unit will wait without receiving data before alarming.
Apply Alarm on Days
displays a menu where the seven days of the week are listed, and each can be toggled
ON or OFF to designate whether this particular No-Data Alarm is active on that day. Default setting is ON for
Monday thru Friday, and OFF for Saturday and Sunday.
Enable Ports
displays a menu where the installed serial ports are listed and each can be toggled ON or OFF to
designate whether this particular No-Data Alarm is active on that port. Default setting is OFF for all ports.
Add Exclusion / Delete Exclusion
allow you to add or delete specific dates when this No-Data Alarm should
“take the day off”. For example, Christmas is a day you might want to add here. Select Add Exclusion and enter
12/25
. To delete a date, select Delete Exclusion and type in the date you want to remove. After an exclusion
date is added it appears in the brackets at the bottom of the menu. 15 dates can be entered to be excluded.