SiteBoss 571 - Auxiliary Sensor Settings
A) Fuel Sensor Settings
B) AC Power Monitor Settings
The Fuel Sensor Settings option displays a submenu for configuring up to three Fuel Sensors.
The AC Power Monitor Settings menu displays a submenu for configuring up to six AC Power Monitors.
Fuel Sensor Settings
This menu tree is used to configure up to three Fuel Sensors. Refer to the Fuel Sensor Feature Guide on the
Asentria Product Information Portal
for a more in-depth explanation of configuring fuel sensing or contact
SiteBoss 571 - Fuel Sensor Settings
A) Fuel Sensor 1
B) Fuel Sensor 2
C) Fuel Sensor 3
Enter your Selection: A
SiteBoss 571 - Settings for Fuel Sensor 1
A) Enable [OFF]
B) Sensor Type [CURRENT]
C) Name [unnamed]
D) Level Measurement Settings
E) Volume Calculation Settings
F) Volume Event Settings
G) Disconnect Event Settings
H) System Reporting Settings
Enable
This is an ON/OFF toggle to enable the fuel sensor. The default setting is OFF.
Sensor Type
The Sensor Type toggles between CURRENT, VOLTAGE and RESISTIVE FLOAT. The default is Current.
Name
The Name option is an alphanumeric field that allows you to name this fuel sensor (maximum length 60
characters). The default setting is ‘unnamed’.
This option displays a submenu to set up the fuel level measurement settings.
This option displays the menu for configuring the prerequisite measurements taken that apply to the dimensions of
the fuel tank, including custom tank settings.
This option displays the menu for configuring alarm notifications based on changes in the fuel level.
This option displays the menu for configuring alarm notifications of the fuel sensor being disconnected.
System Reporting Settings