Asentria SiteBoss 571 UserManual
Page 54
TAP Init String
This option is the user-defined modem initialization string used only when the modem is making an alphanumeric
modem callout. The default setting is ATM0. (Maximum length 126 chars) Note: Make sure to enter 'AT' at the
beginning of this initialization string.
TAP Uses 8N1 Data/Parity/Stop
This is an ON/OFF toggle, to force the TAP initialization string data/parity/stop settings to 8N1. Default setting is
OFF.
Caller ID Security
This selection displays a menu that allows configuration of from one to twenty inbound phone numbers. If this
feature is enabled then the modem will only answer calls from the specified numbers.
Note:
Caller ID must be available on the phone line connected to the S571 for this feature to work.
SiteBoss 571 - Caller ID Security
A) Enable [OFF]
B) Caller ID 1 []
...
U) Caller ID 20 []
V) Add Number From Log List
Enable
This is an ON/OFF toggle to enable Caller ID restrictions. When enabled, the S571 will only answer the modem if
Caller ID indicates one of the allowed phone numbers is connecting. The default setting is OFF.
Caller ID
n
Select one of these options to add or change a specified number. You are allowed to use simple wildcards in
phone numbers: An asterisk (*) wildcard allows for any number of digits to appear to the right of that position. A
question mark (?) matches any single digit. If no numbers are defined in this menu, all incoming calls are accepted
(Maximum length 47 chars).
Add Number From Log List
Choosing this option will displays a list of phone numbers that have recently dialed into the S571 for addition to this
list.
Setting Key:
modem.hsk
Values are
RTS
(default),
None
and
Xon
. RTS means that on serial pass-through, the modem uses RTS
handshaking; None means no handshaking is used; and Xon means XON/XOFF characters are used.
Wireless Modem
Below is a brief description of the menu configurations options. For a complete description of the setup and
operation of the Wireless Modem, please refer to the
If the optional Wireless Modem expansion card is not installed in the SiteBoss, this menu is displayed, but
changing any of the settings will not do anything, except for the PPP/Wireless User Name and Password settings.
SiteBoss 571 - Wireless Modem Settings
A) Mode [PERMANENT]
B) APN []
C) PIN []
D) PPP/Wireless User Name []
E) PPP/Wireless Password [********]
F) Default Route Enable [ON]
G) Firewall [OFF]
H) Advanced Settings