Very High Event Class
This field sets the class for the event. When this option is selected, a list of the classes previously defined in the
is displayed. Select one to be assigned to this event. The default is Info.
Return to Normal Settings Setup
This is a menu for configuring any actions or notifications when the temperature reading returns to the range below
the configured high temperature setting and above the configured low temperature settings.
SiteBoss 571 - Internal Temperature Event Settings
A) Return to Normal Event Actions []
B) Return to Normal Event Trap Number [120]
C) Return to Normal Class [Info]
Return to Normal Event Actions
This option displays the Actions List, a menu where the action string for the event is configured. This field will be
empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been configured.
Refer to the
Return to Normal Event Trap Number
This field sets the trap number which can be useful when using SNMP trap managers that employ a trap
numbering system to help identify incoming traps. The default trap number for Temperature Events is 120, but any
number in the alternate range of 1000
– 1199 can be used.
Return to Normal Class
This field sets the class for the event. When this option is selected, a list of the classes previously defined in the
is displayed, from which you can select one to be assigned to this event.
Contact Closure
n
The S571 has four internal contact closures. They are located under the USB ports on the front panel. The contact
closures may be configured to alarm in either the open or closed state, depending on the needs of the attached
device.
SiteBoss 571 - Internal Contact Closure Event 1
A) Sensor Name [unnamed]
B) Contact Closure Enabled [OFF]
C) Event State [CLOSED]
D) Event Threshold [2]
E) Return to Normal Threshold [2]
F) Event State Actions []
G) Return to Normal Actions []
H) Event State Class [Info]
I) Return to Normal Class [Info]
J) Event Trap Number [110]
K) Return to Normal Trap Number [110]
L) Active Alarm Alias []
M) Inactive Alarm Alias []
N) Override Global Reminder Interval [OFF]
O) Individual Reminder Interval (minutes) [120]
Sensor Name
An alphanumeric field that allows you to name this contact closure (maximum length 60 characters). The default
setting is ‘unnamed’.
Contact Closure Enabled
This is an ON/OFF toggle to enable this contact closure. The default setting is OFF.