Asentria SiteBoss 571 UserManual
Page 73
Event State
This is an OPEN/CLOSED toggle that determines whether an event will be triggered when the contact closure
circuit is opened or closed. The default state is CLOSED.
Event / Return to Normal Threshold
A field that sets the number of seconds (0-255) the sensor must remain in, or be out of, the event state before an
event action occurs. The default setting is 2 seconds.
Event State / Return to Normal Actions
Choosing this option displays the Actions List, a menu where the action string for the event is configured. This
field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to the
Event State / Return to Normal Class
This option is to set the class for the event. When this option is selected, a list of the classes previously defined in
the
is displayed. Select one to be assigned to this event. The default is Info.
Event / Return to Normal Trap Number
This option is for setting the trap number which can be useful when using SNMP trap managers that employ a trap
numbering system to help identify incoming traps. The default trap number for Contact Closure Events is 110, but
any number in the alternate range of 1000
– 1199 can be used.
Active Alarm Alias
You can use this option to define a customized name representing the active alarm state. This would be used
when reporting active events for this sensor (maximum length 60 characters).
Inactive Alarm Alias
This option functions the same as Active Alarm Alias, but used with Return to Normal events (maximum length 60
characters).
Override Global Reminder Interval
This option is an ON/OFF toggle to override the global reminder interval. If this is set to ON a specific reminder
interval can be set for this event. The default setting is OFF.
Individual Reminder Interval (minutes)
This field sets the time in minutes (0
– 65535) for an action to be repeated if the contact closure that triggered the
alarm is still in the “active” state. When the sensor has been returned to the inactive state, the reminder interval is
no longer in effect. The default setting is 120 minutes.
Output
n
These are the control and alarm settings for the nine fuse protected DC power distribution outputs.
SiteBoss 571 - External Output Event 1
Device Number: 0 Device ID: 0C000000 Device Name: Internal Se
A) Name [unnamed]
B) State [ON]
C) Active Alias [On]
D) Inactive Alias [Off]
E) Active Color [#E00303]
F) Inactive Color [#2FCF17]
G) Active Event Actions []
H) Inactive Event Actions []
I) Active Event Trap Number [150]
J) Inactive Event Trap Number [150]
K) Active Event Class [Info]
L) Inactive Event Class [Info]
M) Load Shedding Settings