MAIN Power Distribution Settings
The Main Power Distribution Settings include the total current drawn by all devices, including the SiteBoss itself.
The main voltage reading is the total voltage reading across the main bus bars. Power Distribution Settings allows
the user to configure the Current and Voltage Sensors for power used by the SiteBoss, and the Current and Fuse
Sensors for each of the individual power distribution outputs.
SiteBoss 571 - MAIN Power Distribution Settings
Device Number: 200 Device ID: 0C000000 Device Name: INTERNAL
A) Current Sensor
B) Voltage Sensor
The Current Sensor option will displays the menu for configuring the event setting for the Main Current Sensor
readings. This includes the current drawn by all devices including the SiteBoss.
The Voltage Sensor option displays the menu for configuring the Main Voltage Sensor settings and associated
alarm actions.
MAIN Current Sensor Settings
This menu is used to configure alarm events based on the total current readings. This is the total current drawn by
the devices. This value includes the current drawn by the SiteBoss.
SiteBoss 571 - MAIN Current Sensor Settings
Device Number: 200 Device ID: 0C000000 Device Name: Internal
A) Current Sensor Enabled [OFF]
B) Deadband (mA) [100]
C) Very High Event Settings [120000] [] [180] [Info]
D) High Event Settings [100000] [] [180] [Info]
E) Return to Normal Settings [-] [] [180] [Info]
F) Low Event Settings [1000] [] [180] [Info]
G) Very Low Event Settings [0] [] [180] [Info]
Current Sensor Enabled
This is an ON/OFF toggle to enable this sensor.
Deadband (mA)
This sets a range (in milliamps) on either side of an amperage setting that prevents the event from repeatedly
going in and out of the "alarm state" as the actual amperage fluctuates above and below the amperage setting.
Very High / High / Low / Very Low Event Settings
These settings display menus where the amperage at each level can be configured to alarm along with the
action(s) to occur, trap number, and class. In the case of Very High or High levels, the alarm will occur as the
amperage rises above the setting. In the case of Low or Very Low, the alarm will occur as the amperage drops
below the setting.
This option displays a menu where actions can be configured for events as the amperage readings return to a
normal state.
Very High / High / Low / Very Low Current Sensor Event Settings
The menu for setting Very High Event Value settings is shown. The menus for High/Low/Very Low are identical.