SiteBoss 571 MAIN Current Sensor Event
Device Number: 200 Device ID: 0C000000 Device Name: INTERNAL
A) Very High Event Value (mA) [120000]
B) Very High Event Actions []
C) Very High Event Trap Number [180]
D) Very High Event Class [Info]
Very High Event Value (mA)
This sets the amperage (in milliamps) at which the Very High Event Actions will be triggered.
Very High Event Actions
This selection displays the Actions List, a menu where the action string for the event is configured. This field will
be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to the
Very High Event Trap Number
Use this option to set the trap number which can be useful when using SNMP trap managers that employ a trap
numbering system to help identify incoming traps. The default trap number for Current Sensor Events is 180, but
any number in the alternate range of 1000
– 1199 can be used.
Very High Event Class
Select this option to set the class for the event. When this option is selected, a list of the classes previously
defined in the
is displayed, from which you can select one to be assigned to this event.
Return to Normal Settings
This menu is used to configure actions for the SiteBoss to take when the current readings return to the defined
normal range.
SiteBoss 571 MAIN Current Sensor Event
Device Number: 200 Device ID: 0C000000 Device Name: INTERNAL
A) Return to Normal Event Actions []
B) Return to Normal Event Trap Number [180]
C) Return to Normal Event Class [Info]
Return to Normal Event Actions
This option displays the Actions List, a menu where the action string for the event is configured. This field will be
empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been configured.
Refer to the
Return to Normal Event Trap Number
Use this to set the trap number which can be useful when using SNMP trap managers that employ a trap
numbering system to help identify incoming traps. The default trap number for Current Sensor Events is 180, but
any number in the alternate range of 1000
– 1199 can be used.
Return to Normal Event Class
Select this option to set the class for the event. When this option is selected, a list of the classes previously
defined in the
is displayed, from which you can select one to be assigned to this event.
MAIN Voltage Sensor Events
The main voltage reading is the total voltage reading across the main bus bars. Use this menu to configure
actions for the SiteBoss to take if the voltage above or below user defined ranges.