Asentria SiteBoss 571 UserManual
Page 79
SiteBoss 571 MAIN Voltage Sensor Event
Device Number: 200 Device ID: 0C000000 Device Name: INTERNAL
A) Return to Normal Event Actions []
B) Return to Normal Event Trap Number [190]
C) Return to Normal Event Class [Info]
Return to Normal Event Actions
This selection displays the Actions List, a menu where the action string for the event is configured. This field will
be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to the
for more information.
Return to Normal Event Trap Number
Set the trap number which can be useful when using SNMP trap managers that employ a trap numbering system
to help identify incoming traps. The default trap number for Main Voltage Sensor Events is 190, but any number in
the alternate range of 1000
– 1199 can be used.
Return to Normal Event Class
Set the class for the event. When this option is selected, a list of the classes previously defined in the
is displayed, from which you can select one to be assigned to this event.
Unnamed
n
- Power Output Current Sensor Events
These menus are used to configure the current sensor alarm actions and thresholds for each individual power
output.
SiteBoss 571 - Power Distribution Settings for Output 1
Device Number: 200 Device ID: 0C000000 Device Name: Internal Se
A) Current Sensor
B) Fuse Sensor
This option displays a menu where you can enable the Current Sensor for the individual Power Output and
configure Sensor Event settings.
This option brings up a menu where you can configure Fuse Sensor events and alarm actions.
Current Sensor Settings for Output
n
These menus are used to configure the current sensor alarm actions and thresholds for each individual power
output.
SiteBoss 571 - Current Sensor Settings for Output 1
Device Number: 200 Device ID: 0C000000 Device Name: Internal
A) Current Sensor Enabled [OFF]
B) Deadband (mA) [100]
C) Very High Event Settings [12000] [] [180] [Info]
D) High Event Settings [10000] [] [180] [Info]
E) Return to Normal Settings [-] [] [180] [Info]
F) Low Event Settings [1000] [] [180] [Info]
G) Very Low Event Settings [0] [] [180] [Info]
Current Sensor Enabled
This is an ON/OFF toggle to enable this sensor.