Asentria SiteBoss 571 UserManual
Page 82
Inactive Alarm Alias
Use this field to set a customized name representing the Return to Normal events. The default setting is OK.
EventSensor Slots (Slot B Through Q)
The display for each EventSensor will vary depending on configuration. For example, an EventSensor could be
either internal or external. EventSensors can be configured with varying combinations of I/O types. Choosing an
EventSensor option will bring up a menu where event thresholds and actions can be configured. Refer to the
EventSensors Feature Guide on the
Asentria Product Information Portal
or contact
more information.
SiteBoss 571 - Sensor Events Menu
Name ID Alive Number Configuration
A) Internal Sensors -------- - 200 1-TS 4-CC 5-PW
B) <none>
C) <none>
D) <none>
E) PB6 51130000 Y 4 12-PW
F) PB2 4F140000 Y 5 9-PW
G) <none>
H) <none>
I) <none>
J) <none>
K) <none>
L) ES-R 591A0000 Y 11 1-VS
M) <none>
N) <none>
O) <none>
P) <none>
Q) <none>
R) Auxiliary Sensor Settings
S) Sensor Unresponsive Settings
T) Load Shedding Settings
The SiteBoss supports a maximum of 16 external EventSensor slots. Some larger EventSensors occupy more
than one slot. For example, the ES-CCU32 requires two slots and the ES-CCU64 requires four.
Some external EventSensors have dip switches on the EventSensor that will need to be set to the slot number
you wish that sensor to display at. On the command interface menu option "B" is slot "1" and option "Q" would
be slot "16". Option "A" is the Internal IO card option, which is referred to as slot "200".
1 = DIP Switch up 0 = DIP Switch down
For one wire SensorJack sensors, the settings slot will automatically be assigned to it if one is available.
Auxiliary Sensor Settings
The Auxiliary Sensor Settings contains submenus for the non-EventSensor sensors including the Fuel Sensor
and AC Power Monitor.