Asentria SiteBoss 571 UserManual
Page 84
Level Measurement Settings
This menu is used to configure the fuel level measurement settings.
SiteBoss 571 - Level Measurement Settings for Fuel Sensor 1
A) Analog Input Eventsensor [200]
B) Analog Input Point [1]
C) Distance Unit [CM]
D) Raw Value Top [5000]
E) Top Offset [0.0]
F) Raw Value Bottom [0]
G) Bottom Offset [0.0]
Analog Input EventSensor
This field sets the slot number of the EventSensor associated with this fuel sensor. Allowed values are 200 (for
Internal EventSensor) or 1
– 16. The default value is 200.
Analog Input Point
This field sets the input point on the EventSensor that is associated with this fuel sensor. Range is 1-48. The
default value is 1.
Distance Unit
This option toggles between INCH and CM to specify the distance unit to be used when setting an indicated tank
dimension. The default value is CM.
Raw Value Top
This field sets the analog input reading that corresponds to the SENSOR FULL point. This is an integer with range
of 0 to 2,147,483,647. The default value is 5000.
Top Offset
The Top Offset defines the distance, in the specified distance unit, between the SENSOR FULL point and the
TANK FULL point. This is a floating-point value with range of -1,000 to +1,000. A positive value means the
SENSOR FULL point is above the TANK FULL point, and a negative value means it is below. The default value is
0.0.
Raw Value Bottom
This field sets the analog input reading that corresponds to the minimum fluid height measurable by the fuel
sensor. This is an integer with range of 0 to 2,147,483,647. The default value is 0.
Bottom Offset
The Bottom Offset defines the distance, in the specified distance unit, between the SENSOR EMPTY point and the
TANK EMPTY point. This is a floating-point value with range of -1,000 to +1,000. A positive value means the
SENSOR EMPTY point is above the TANK EMPTY point and a negative value means it is below the TANK
EMPTY point. The default value is 0.0.
Volume Calculation Settings
The Volume Calculations Settings is the menu for configuring the prerequisite measurements taken that apply to
the dimensions of the fuel tank, including custom tank settings.
SiteBoss 571 - Volume Calculation Settings for Fuel Sensor 1
A) Tank Shape [LINEAR]
B) Tank Height [100.0]
C) Tank Dimension A [0.0]
D) Tank Dimension B [0.0]
E) Tank Volume [200.0]
F) Volume Unit [Liters]
G) Input Filter Averaging [1]
H) Custom Tank Settings