Enable Event
This is an ON/OFF toggle to enable the Scheduled Event. The default setting is OFF.
Event Actions
This option
displays the Action List, a menu where the action string for the event is configured. This field will be
empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been configured.
Refer to
in the Features chapter for more information.
Event Message
Use this field to set
the text string to be delivered with this event’s action. The default setting is "Scheduled Event
n
“ (maximum length 126 chars).
Event Class
Set the class for the event. When this option is selected, a list of the classes previously defined in the
is displayed, from which you can select one to be assigned to this event.
Trap Number
Set the number to be sent with any SNMP traps for this event. The default is 506, but trap number can also be set
in the range of 1000
– 1199 as needed.
Event Time
day
Use this option to set the time (24 hour clock) each day at which the Scheduled Event action will occur. If no time
is configured for any day, this menu displays OFF. The default setting is OFF for each day.
Add Exclusion / Delete Exclusion
These fields allow you to add
or delete specific dates when this Scheduled Event should “take the day off”. For
example Christmas is a day you might want to add here. Select Add Exclusion and type in
12/25
. To delete a
date, you select Delete Exclusion and type in the date you want to remove. After an exclusion date is added it
appears in the brackets at the bottom of the menu. Up to fifteen dates can be entered to be excluded.
Serial Handshaking Alarm Settings
Serial Handshaking Alarms allows the SiteBoss to monitor each of its serial ports and alert you if the DTR signal
from the connected devices drops low. This would be an indicator that the connected device has failed, the cable
between the SiteBoss and the device has been disconnected, or a number of other reasons depending on the
device. It can also alert you when the DTR signal goes high again.
SiteBoss 571 - Serial Handshaking Alarm Settings
A) I/O 1 Serial Handshaking Alarms [OFF]
. . .
P) I/O 16 Serial Handshaking Alarms [OFF]
I/O
n
Serial Handshaking Alarms
These options display a menu for configuring alarming on serial DTR handshaking conditions for the specified
serial port.
SiteBoss 571 - I/O 1 Serial Handshaking Alarms
A) Serial Handshaking Low Alarm Enable [OFF]
B) Serial Handshaking Low Alarm Actions []
C) Serial Handshaking Low Alarm Message [Handshake Low]
D) Serial Handshaking Low Alarm Class [Info]
E) Serial Handshaking Low Trap Number [510]
F) Serial Handshaking High Alarm Enable [OFF]
G) Serial Handshaking High Alarm Actions[]
H) Serial Handshaking High Alarm Message[Handshake High]
I) Serial Handshaking High Alarm Class [Info]
J) Serial Handshaking High Trap Number [510]