Asentria SiteBoss 571 UserManual
Page 99
Return to Normal Class
Set the class for the alarm. When this option is selected, a list of the classes previously defined in the
is displayed, from which you can select one to be assigned to this event.
Reset Event Settings
The Reset Event Settings are used to configure event actions to be performed after the unit has been
restarted. These actions would be executed regardless of whether the unit was reset via a restart command
or by power cycling.
SiteBoss 571 - Reset Event Settings
A) Enable Event [OFF]
B) Event Actions []
C) Event Message [Reset Event]
D) Event Class [Info]
E) Event Trap Number [543]
F) Delay After Reset (seconds) [0]
Enable Event
This is an ON/OFF toggle to enable the Reset Event. The default setting is OFF.
Event Actions
Choosing this option displays the Actions List, a menu where the action string for the event is configured. This
field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have
been configured. Refer to
Event Message
Set the text string to be delivered with this event’s action. The default setting is "Reset Event" (maximum
length 80 characters).
Event Class
Set the class for the event. When this option is selected, a list of the classes previously defined in the
is displayed. Select one to be assigned to this event. The default is Info.
Event Trap Number
Set the number to be sent with any SNMP traps for this event. The default is 543, but the trap number can
also be set in the range of 1000
– 1199 as needed.
Delay After Reset (seconds)
Enter the number of seconds to wait after unit finishes booting before executing the Event Action(s) that have
been set for this event. The default is 0, maximum is 3600 (1 hour).
Event Message Settings
This menu is used to customize the event messages that appears in traps, Emails, etc.
SiteBoss 571 - Event Message Settings
A) Include Date and Time [ON]
B) Include Site Name [ON]
C) Include Sensor ID [ON]
D) Include User Defined Name [ON]
E) Include User Defined State [ON]
F) Include Event Class [ON]
Include Date and Time / Site Name / Sensor ID / User Defined Name / User Defined State
/ Event Class
All of these options are each ON/OFF toggles to permit customization of the event message that appears in SNMP
traps, Emails, SMS messages, pages, etc. sent by the S571. The default setting for each is ON.