Doc ID : ADR111A_IM_01
Ref ID : ADR111A/IM/CS
Rev No. : 04
Page No. : 78 of 127
ADR111A /
ADR211A
Time Synchronization – For ASHIDA RTV2 IEDs on Modbus, time synchronization is possible via a broad cast
command to 800H (4x02049 through 4x02052). The format is Inverted IEC 870-5-4 CP56Time2a.
Words
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
1
0
0
0
0
0
0
0
0
Year
00….99
2
0
0
0
0
Month
Day of
Week
Day of Month
1...12 1…7 1…31
3
Hours
Iv0 Minutes
0….23 0….59
4
Milliseconds Hi
Milliseconds Lo
0…..59999 (
mill seconds)
Su
(=0 standard, =1 Summer Time)
iv
(=0 valid, =1 nonvalid or nonsynchronized system case)
First Day of week is Monday
Sr.
No.
Function
Code
Register
No. of
Regs
Format
Reg.
Type
Address
Map
3
Time
Synchronization
(Unicast/Broadcast)
03/16
Year
1
16 bit
R/W
4x02049
Month- Day
1
16 bit
R/W
4x02050
Hour, Min
1
16 bit
R/W
4x02051
Milliseconds
1
16 bit
R/W
4x02052
Sr.
No.
Function
Code
Register
No. of
Regs
Format
Reg.
Type
Address
Map
4
Status and Logical
Status
02
Relay Error
1
1 bit
R
1x32773
Test
1
1 bit
R
1x32774
General Start
1
1 bit
R
1x32777
Start I>
1
1 bit
R
1x32778
Start I>>
1
1 bit
R
1x32779
General Trip
1
1 bit
R
1x32780
Summary of Contents for ADR111A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 27: ...Page intentionally Left Blank...
Page 42: ...Page intentionally Left Blank...
Page 52: ...Page intentionally Left Blank...
Page 64: ...Page intentionally Left Blank...
Page 68: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 84: ...Page intentionally Left Blank...
Page 104: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 119: ...Doc ID ADR111A_IM_01 Ref ID ADR111A IM DR Rev No 04 Page No 119 of 127 ADR111A ADR211A...
Page 120: ...Page intentionally Left Blank...
Page 128: ......