Doc ID : ADR111A_IM_01
Ref ID : ADR111A/IM/TC
Rev No. : 04
Page No. : 123 of 127
ADR111A /
ADR211A
11
TESTING AND COMMISSIONING
11.1
Commissioning Test, Equipment Required
The following connection tests help you enter settings into the ADR111A/ ADR211A and
verify that the relay is properly connected.
Brief functional tests ensure that the relay settings are correct. It is unnecessary to test every
element, timer, and function in these tests. Modify the procedure as necessary to conform to
your standard practices. Use the procedure at initial relay installation; the user need not
repeat it, unless major changes are made to the relay electrical connections.
The ADR111A/ ADR211A installed and connected according to your protection design.
•
Digital Multimeter True RMS
•
Timer with precision 1ms.
•
Required Auxiliary supply
•
For Calibration and measurement check & Pick up test, time test, logic operation test
use Power system Simulator DOBEL make F6150 or any Protective relay ac test source:
•
single-phase current source.
•
A PC with serial port, terminal emulation software, and serial communications cable with
the following software (for ADR211A)
•
For IEC 60870-5-103 communication check: Ashida Relay Talk software.
11.2
Checking of External Circuitry
Connection Tests
Step 1:
Remove control ac signals from the ADR211A by opening the appropriate
breaker(s) or removing fuses
Step 2:
Isolate the relay TRIP output contact
Step 3:
Verify correct ac and dc connections by performing point-to-point continuity
checks on the associated circuits.
Step 4:
Apply ac or dc control voltage to the relay. After the relay is energized, the front-
panel green ON LED should illuminate.
Step 5:
Use the appropriate serial cable (USB to serial Cable or equivalent) to connect a
PC to the relay.
Step 6:
Start the PC terminal emulation software and establish communication with the
relay.
Step 7:
Set the correct relay time and date by using either the front panel or serial port
commands
Step 8:
Verify the relay ac connections.
Summary of Contents for ADR111A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 27: ...Page intentionally Left Blank...
Page 42: ...Page intentionally Left Blank...
Page 52: ...Page intentionally Left Blank...
Page 64: ...Page intentionally Left Blank...
Page 68: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 84: ...Page intentionally Left Blank...
Page 104: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 119: ...Doc ID ADR111A_IM_01 Ref ID ADR111A IM DR Rev No 04 Page No 119 of 127 ADR111A ADR211A...
Page 120: ...Page intentionally Left Blank...
Page 128: ......