ADR141A /
ADR241A
Doc ID : ADR241A_IM_01
Ref ID : ADR241A/IM/SS
Rev No.
: 02
Page No. : 78 of 150
6.2
Cold Load
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
000
000 – 099
This setting specifies to enter the set password
2.
CL Enable
Yes
01 – 02 (1= Yes, 2= No)
This setting determine to enable (turn on) or disable (turn off) the Cold load function.
3.
CL Timer
1.00s
0.01 – 10.0s in steps of 0.10s
This setting controls the period of time for which the relevant over current and ground over current
settings are altered or inhibited following circuit breaker closure.
4.
CL IP>
100%
5% – 250% in step of 1%
This setting determines Pick-up setting for first stage over current element.
5.
CL IP>TMS
1.00
0.01 – 1.50 in steps of 0.005
This setting for the time multiplier setting to adjust the operating time of the IDMT characteristic.
6.
CL IP>>
100%
50% – 3000%
in step of 1%
This setting determines Pick-up setting for second stage over current element.
7.
CL IE>
100%
5% – 250% in step of 1%
This setting determines Pick-up setting for first stage Ground over current (Measured) element.
8.
CL IE>TMS
1.00
0.01 – 1.50 in steps of 0.005
This setting for the time multiplier setting to adjust the operating time of the IDMT characteristic.
9.
CL IE>>
100%
50% – 3000%
in step of 1%
This setting determines Pick-up setting for second stage Ground over current (Measured) element.
10.
CL IP> Curve
C1
Normal Inverse1 (C1)/ Normal Inverse2
(C2)/ Very Inverse (C3)/ Extremely
Inverse (C4)/ Extremely Inverse (C4A)/
Long Time Inverse (C5)/ Definite Time
(C6)
This setting determines the tripping characteristic for the first stage over current element.
11.
CL IE> Curve
C1
Normal Inverse1 (C1)/ Normal Inverse2
(C2)/ Very Inverse (C3)/ Extremely
Inverse (C4)/ Extremely Inverse (C4A)/
Long Time Inverse (C5)/ Definite Time
(C6)
This setting determines the tripping characteristic for the first stage Ground over current element.
12.
CL IP> C6 Time
1.00s
0.00 – 99.9s in steps of 0.10s
This setting is used to set the time-delay for the Definite Time (DT) setting if selected for first stage over
current element.
13.
CL IE> C6 Time
1.00s
0.00 – 99.9s in steps of 0.10s
Summary of Contents for ADR141A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 28: ...Page intentionally Left Blank...
Page 43: ...Page intentionally Left Blank...
Page 53: ...Page intentionally Left Blank...
Page 69: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 80: ...Page intentionally Left Blank...
Page 92: ...Page intentionally Left Blank...
Page 122: ...Page intentionally Left Blank...
Page 136: ...Page intentionally Left Blank...
Page 140: ...ADR141A ADR241A Doc ID ADR241A_IM_01 Ref ID ADR241A IM DR Rev No 02 Page No 140 of 150...
Page 141: ...Page intentionally Left Blank...
Page 151: ......