Post instillation / Commissioning observation
After successful installation confirm amount of existing load current in each phase (R, Y and
B) and Earth Fault (EF). This can be confirmed with Analogue/ Digital current meter available
on panel with relay primary and secondary current measurement window. In normal
balanced load condition, the i.e. current should be very low.
11.4
Relay Testing
Relay Calibration & Measurement
Before conducting actual test, confirm relay calibration by following method.
•
Connect ADR141A/ ADR241A relay to current injector and timer.
•
Following chart shows terminal numbers of connections.
Source Terminal
Relay Terminal
Relay Connection
Current Source
A1 – A2
Current R-CT _1A
A3 – A4
Current R-CT _5A
A5 – A6
Current Y-CT _1A
A7 – A8
Current Y-CT _5A
A9 – A10
Current B-CT _1A
A11 – A12
Current B-CT _5A
A13 – A14
Current EF-CT _1A
A15 – A16
Current EF-CT _5A
Power Supply (+ / -)
C1 – C3
Power Supply (+ / -)
Logic Input
B2 – B4
Status 1
B3 – B5
Status 2
B6 – B8
Status 3
B7 – B9
Status 4
Logic Output
C2 – C4
TRIP 1
C5 – C7
TRIP 2
C6 – C8
ANN. 1
C9 – C11
ANN. 2
C10 – C12
ANN. 3
C13 – C15
ANN. 4
C14 – C16
BF
B10 – B11 – B12
TCS
Step1.
Connect all terminals as per the chart.
Step2.
Adjust rated CT Secondary Current 1A/5A. Observe the current value from
measurement menu. The actual current should match with relay display.
Step3.
Repeat the same procedure for other element.
Summary of Contents for ADR141A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 28: ...Page intentionally Left Blank...
Page 43: ...Page intentionally Left Blank...
Page 53: ...Page intentionally Left Blank...
Page 69: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 80: ...Page intentionally Left Blank...
Page 92: ...Page intentionally Left Blank...
Page 122: ...Page intentionally Left Blank...
Page 136: ...Page intentionally Left Blank...
Page 140: ...ADR141A ADR241A Doc ID ADR241A_IM_01 Ref ID ADR241A IM DR Rev No 02 Page No 140 of 150...
Page 141: ...Page intentionally Left Blank...
Page 151: ......