Externally measured ground over current through CBCT 

 

Harmonic blocking / Unblocking for 
Over Current Protection 
(50H/51H/50NH/51NH): 

Harmonic blocking / unblocking feature 

equipped in ADR244A relay provides stability 

on inrush current during transformer 

energization. Harmonic blocking/unblocking 

feature is independent for each stage of 

phase and ground over current protection. 

 

 

 

Additional functions (CLP & SOTF): 

ADR244A  provides the cold load pick up 

(CLP) and switch on to fault (SOTF) as 

additional functions. User can select the one 

of this function for application. Cold load pick 

up function provided in relay for multiple 

applications.  The  application of this feature 

can be use to avoid wrong operation on 

inrush current during transformer 

energization without compromising sensitivity 

of over current protection. 

 

 

 

The  ADR244A  provides SOTF function to 
protection feeder against switch on to fault 
condition during feeder/transformer 
energization. 
 

 

 

 

Negative Phase Sequence Over 

Current Protection (46): 

Two  independent stages of Definite and 

Inverse time Negative sequence over current 

protection will be providing back up 

protection of over head transmission line / 

underground cable / feeder against 

unbalanced faults, very high resistive 

phase/ground faults and unbalanced loads. 

Summary of Contents for ADR244A

Page 1: ...n Control and Monitoring functions for Induction motors Draw out Non draw out versions are available based on ordering information Functional Overview Key Protection Control Functions Draw out Non dra...

Page 2: ...isturbance Recording 10 nos Event Recording 512 nos Fault Recording on HMI display 10 nos Non Volatile memory Fully communicable with IEC standard open protocol IEC60870 5 103 Separate communication p...

Page 3: ...ith non directional over current protection will be providing greater selectivity flexibility and sensitivity to users for better relay co ordinations ADR244A relay provides inverse time over current...

Page 4: ...e time inverse time internally derived zero sequence over current 3I0 protection to detects asymmetrical faults in electrical network It can apply to over head transmission line underground cable and...

Page 5: ...an select the one of this function for application Cold load pick up function provided in relay for multiple applications The application of this feature can be use to avoid wrong operation on inrush...

Page 6: ...age Broken Conductor Protection 46BC ADR244A equipped with broken conductor detection protection Broken conductor condition can be detected by ratio of Negative sequence current to Positive sequence c...

Page 7: ...e alarm whenever the circuit breaker control DC circuitry gets interrupted The ADR244A is having 4 separate digital opto coupler status input which can be used to continuously monitor heartiness of tr...

Page 8: ...y Disturbance records can be saved in IEEE COMTRADE format and same can be analyzed in disturbance analysis software Fault recording ADR244A relay is providing fault record facility The fault records...

Page 9: ...4 5 Differential Mode 2kV Common Mode 4kV 1 2 50 s 8 20 s 5 surges of each polarity 5 Power Frequency Immunity Test IEC60255 22 7 Class A 6 Pulse Magnetic Field Immunity Test IEC61000 4 9 TEST LEVEL 5...

Page 10: ...0M 500V DC Environmental tests 14 Cold test IEC 60068 2 1 15 Dry heat test IEC 60068 2 2 16 Damp heat test steady state IEC 60068 2 78 17 Change of Temperature IEC 60068 2 14 18 Damp heat test cyclic...

Page 11: ...Response Test IEC 60255 21 2 Class 2 3 shocks of 10gn peak acceleration and 11ms pulse in each of two opposite direction No of axis 3 28 Seismic Test IEC 60255 21 3 Class 2 Sweep 1 Axis a sweep rate o...

Page 12: ...ADR244A Doc ID ADR244A PC 01 Rev No 01 Page No 12 of 15...

Page 13: ...ADR244A Doc ID ADR244A PC 01 Rev No 01 Page No 13 of 15...

Page 14: ...ADR244A Doc ID ADR244A PC 01 Rev No 01 Page No 14 of 15...

Page 15: ...trademark or registered trademark of their respective holders No ASHIDA trademarks may be used without written permission The information in this document is provided for informational use only and i...

Reviews: