INSTALLATION
BACK WALL
2”
6”
USA 6”
CANADA 8”
FLOOR PROTECTION
USA 6”
CANADA 18”
2”
FLOOR
PROTECTION
USA 6”
CANADA 8”
USA 6”
CANADA 18”
Alcove Dimensions
36”
35”
40”
INSTALLATION OPTIONS
READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR PELLET STOVE. FAILURE TO FOLLOW
INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH!
(See speci
fi
c installation details for clearances and other installation requirements)
A
Freestanding Unit
—supported by pedestal/legs and placed on a non-combustible
fl
oor surface in compliance with clearance
requirements for a freestanding stove installation.
An
Alcove Unit
—supported by pedestal/legs and placed on a non-combustible
fl
oor surface in compliance with clearance requirements
for an alcove installation.
Your pellet stove may be installed to code in either a
conventional
or
mobile home
(see SPECIAL MOBILE HOME REQUIREMENTS).
The installation must comply with the Manufactured Home and Safety Standard (HUD), CFR3280, Part 24.
It is recommended that only a authorized technician install your pellet stove, preferably an NFI certi
fi
ed specialist.
DO NOT CONNECT THIS UNIT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
The use of other components other than stated herein could cause bodily harm, heater damage, and void your warranty.
IMPROPER INSTALLATION:
The manufacturer will not be held responsible for damage caused by the mal-
function of a stove due to improper venting or installation. Call (800) 750-2723 and/or consult a professional
installer if you have any questions.
CLEARANCES
Your pellet stove has been tested and listed for installation in residential, mobile home, and alcove applications in accordance with
the clearances given. For safety reasons, please adhere to the installation clearances and restrictions. Any reduction in clearance to
combustibles may only be done by means approved by a regulatory authority.
INSTALL ALL VENTS AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER
When your Pellet Stove Room Heater is being installed on a combustible
fl
oor it is mandatory that a 1/2” (13mm) thick non-combustible
hearth pad be installed under the heater. The non-combustible hearth pad must extend at least 6” beyond the fuel loading and ash removal
openings and at least the depth of the heater plus 6 inches (152mm) out in front of the heater. The
fl
oor protector must extend 2” (51mm)
beyond each side of the exhaust vent. This applies to both freestanding heaters and insert heaters.