9
UVR-HE Series
RCE-EC CONTROL UNIT
• Suitable for wall installation in boxes with 3 type 503 modules.
• Allows to switch the appliance on and off and to set 2 different operating modes:
1. Manual operation
2. Automatic operation
For fan unit configuration and operation, refer to the instruction manual of the RCE-EC control unit included in the package.
9. INSTALLATION AND COMMISSIONING
ALL MAINTENANCE OPERATIONS MUST ALWAYS BE CARRIED OUT WITH THE MACHINE STOPPED AND ELECTRICAL POWER DISCONNECTED
.
• Before carrying out any maintenance operation, disconnect current to the machine by turning the current cut-out knob to “0”.
• It is mandatory to perform all maintenance operations on the unit, respecting the time intervals specified below.
• Only previously trained and qualified personnel can perform maintenance operations.
• If the unit is to be disassembled, protect your hands with work gloves.
• All maintenance operations must be carried out with the machine resting on a horizontal plane, sufficiently strong to withstand the
weight of the machine, NEVER when it is hung on walls or ceilings.
FILTER CLEANING AND MAINTENANCE INSPECTION.
We recommend replacing the filters every 15 or 30 days max, depending on the pollution of the room air. In any case, the filters must
ALWAYS be replaced whenever the relative warning light on the control screen of the unit indicates a high level of clogging of the filters.
• To remove the filter, disassemble the inspection panel and pull out the filter.
• To clean, use a vacuum cleaner or wash with a common detergent in warm water, letting it dry well.
• Always remember to reassemble the filter before starting the unit.