If the door is left open for longer than a preset time, the keypad will generate an 
alarm until the door is closed. The door open time can be programmed from 1 to 
999 seconds. Door position is monitored via the 

Door Position Sensor Input

1.  Put the keypad in 

Program Mode

 by entering the 

Installer Code 

followed by 

the “

”. The keypad will beep twice and the yellow LED will be on and not 

blinking. 

2. Enter “

9 (door open time 1-999) #

”.  

3. Enter “

” to exit Program Mode. The yellow LED will begin blinking. 

To disable the 

Door Propped Open Alarm 

feature - 

1.  Put the keypad in 

Program Mode

 by entering the 

Installer Code 

followed by 

the “

”. The keypad will beep twice and the yellow LED will be on and not 

blinking. 

2. Enter “

9 0 #

”.  

3. Enter “

” to exit Program Mode. The yellow LED will begin blinking. 

Outputs 1 and 2 can be programmed for either momentary or latching operation. 
Momentary operation time can be set for between 1 and 999 seconds. The 
factory default momentary operation time is 2 seconds. 
1.  Put the keypad in 

Program Mode

 by entering the 

Installer Code 

followed by 

the “

”. The keypad will beep twice and the yellow LED will be on and not 

blinking. 

2. Output 1 

Momentary Mode 

  

Enter “

4 0 (output active time 1-999) #”

 

Output 2 

Momentary Mode 

  

Enter “

5 0 (output active time 1-999) #”

 

Output 1 

Latching Mode 

  

Enter “

4 1 #”

 

Output 2 

Latching Mode 

  

Enter “

5 1 #”

 

3. Enter “

” to exit Program Mode. The yellow LED will begin blinking. 

To disable the 

Door Forced Open Alarm 

feature - 

1.  Put the keypad in 

Program Mode

 by entering the 

Installer Code 

followed by 

the “

”. The keypad will beep twice and the yellow LED will be on and not 

blinking. 

2. Enter “

8 0 0 #

”.  

3. Enter “

” to exit Program Mode. The yellow LED will begin blinking. 

DOOR FORCED OPEN ALARM (CONTINUED) 

DOOR PROPPED OPEN ALARM 

MOMENTARY OR LATCHING OUTPUT MODES 

Summary of Contents for Alarm Controls KP-300

Page 1: ...00 645 5538 www alarmcontrols com Model KP 400 is a self contained vandal resistant digital keypad This dual relay output keypad is suitable for residential industrial and commercial installations It...

Page 2: ...ed tool 2 Pass the wire harness through the opening in the back box 3 Mount the back box to the door frame or wall 4 Make all required wiring connections to the terminal blocks 5 Place the keypad face...

Page 3: ...put that switches to ground after the duress code has been entered Output rating Ic max 100mA sink Vc max 24VDC Door Position Sensor Input DOOR SENS A normally closed contact connected to this termina...

Page 4: ...Programming Mode in order to access all keypad configuration settings 1 Put the keypad in Program Mode by entering the Installer Code followed by the The keypad will beep twice and the yellow LED wil...

Page 5: ...tering the Installer Code followed by the The keypad will beep twice and the yellow LED will be on and not blinking 2 Enter 7 2 5 3 Enter to exit Program Mode The yellow LED will begin blinking To dis...

Page 6: ...s 1 and 2 can be programmed for either momentary or latching operation Momentary operation time can be set for between 1 and 999 seconds The factory default momentary operation time is 2 seconds 1 Put...

Page 7: ...ep twice and the yellow LED will be on and not blinking 2 Enter 8 2 1 3 Enter to exit Program Mode The yellow LED will begin blinking To return the keypad to Manual Entry Mode 1 Put the keypad in Prog...

Page 8: ...new installer code For example if you wish to change the Installer Code to 1 2 3 4 you would enter 0 1 2 3 4 7 The keypad will beep twice indicating that the new Installer Code has been accepted 8 Ent...

Page 9: ...DC POWER SUPPLY AC POWER CAN ONLY BE USED WITH AC POWERED ELECTRIC STRIKES MAGNETIC LOCK OR ELECTRIC STRIKE MODEL TS 2 REQUEST TO EXIT STATION OPTIONAL USE N O CONTACTS Output 2 is used to control acc...

Page 10: ...2 REQUEST TO EXIT STATION OPTIONAL USE N O CONTACTS N C DOOR CONTACT Two keypads are required for an inter lock system If either door is open the other door will remain locked TAMPER SWITCH The Tampe...

Page 11: ...5 Relative Humidity Non condensing Environmental Rating Conforms to IP66 Dimensions 3 125 W x 4 5 L x 1 75 to 2 5 D CODES It is recommended that the Installer Code and User Codes be noted here for ref...

Page 12: ...KP 400 Rev E 3 14...

Reviews: