background image

 

12 OR 24V 
AC OR DC 

POWER 

SUPPLY 

AC POWER CAN ONLY 

BE USED WITH 

AC POWERED 

ELECTRIC STRIKES 

MAGNETIC LOCK 

OR 

ELECTRIC STRIKE 

MODEL TS-2 

REQUEST TO  

EXIT STATION 

(OPTIONAL) 

 

USE N/O CONTACTS 

Use N/C contact for magnetic locks and fail-safe 
electric strikes. 

Use N/O contact for fail-secure electric strikes. 

The 1N4004 Diode must be used for DC powered 
electric strike applications. 

12 OR 24V 
AC OR DC 

POWER 

SUPPLY 

AC POWER CAN ONLY 

BE USED WITH 

AC POWERED 

ELECTRIC STRIKES 

MAGNETIC LOCK 

OR 

ELECTRIC STRIKE 

MODEL TS-2 

REQUEST TO  

EXIT STATION 

(OPTIONAL) 

 

USE N/O CONTACTS 

Output 2 is used to control access of Output 1 users. Output 2 must be 
in 

Latching Mode

. Activating Output 2 will lock out Output 1 users. 

Use N/C contact for magnetic locks and fail-safe electric strikes. 

Use N/O contact for fail-secure electric strikes. 

The 1N4004 Diode must be used for DC powered electric strike 
applications. 

Warning! 

Be careful not to lock people inside! 

BASIC WIRING DIAGRAM 

DOOR LOCK INHIBIT WIRING DIAGRAM 

Summary of Contents for Alarm Controls KP-300

Page 1: ...00 645 5538 www alarmcontrols com Model KP 400 is a self contained vandal resistant digital keypad This dual relay output keypad is suitable for residential industrial and commercial installations It...

Page 2: ...ed tool 2 Pass the wire harness through the opening in the back box 3 Mount the back box to the door frame or wall 4 Make all required wiring connections to the terminal blocks 5 Place the keypad face...

Page 3: ...put that switches to ground after the duress code has been entered Output rating Ic max 100mA sink Vc max 24VDC Door Position Sensor Input DOOR SENS A normally closed contact connected to this termina...

Page 4: ...Programming Mode in order to access all keypad configuration settings 1 Put the keypad in Program Mode by entering the Installer Code followed by the The keypad will beep twice and the yellow LED wil...

Page 5: ...tering the Installer Code followed by the The keypad will beep twice and the yellow LED will be on and not blinking 2 Enter 7 2 5 3 Enter to exit Program Mode The yellow LED will begin blinking To dis...

Page 6: ...s 1 and 2 can be programmed for either momentary or latching operation Momentary operation time can be set for between 1 and 999 seconds The factory default momentary operation time is 2 seconds 1 Put...

Page 7: ...ep twice and the yellow LED will be on and not blinking 2 Enter 8 2 1 3 Enter to exit Program Mode The yellow LED will begin blinking To return the keypad to Manual Entry Mode 1 Put the keypad in Prog...

Page 8: ...new installer code For example if you wish to change the Installer Code to 1 2 3 4 you would enter 0 1 2 3 4 7 The keypad will beep twice indicating that the new Installer Code has been accepted 8 Ent...

Page 9: ...DC POWER SUPPLY AC POWER CAN ONLY BE USED WITH AC POWERED ELECTRIC STRIKES MAGNETIC LOCK OR ELECTRIC STRIKE MODEL TS 2 REQUEST TO EXIT STATION OPTIONAL USE N O CONTACTS Output 2 is used to control acc...

Page 10: ...2 REQUEST TO EXIT STATION OPTIONAL USE N O CONTACTS N C DOOR CONTACT Two keypads are required for an inter lock system If either door is open the other door will remain locked TAMPER SWITCH The Tampe...

Page 11: ...5 Relative Humidity Non condensing Environmental Rating Conforms to IP66 Dimensions 3 125 W x 4 5 L x 1 75 to 2 5 D CODES It is recommended that the Installer Code and User Codes be noted here for ref...

Page 12: ...KP 400 Rev E 3 14...