Set-up operation
Warning!
Danger due to faulty commissioning:
In order to ensure the safety of the
product, commissioning must be performed by a qualified person.
ASSA ABLOY
Sicherheitstechnik GmbH
offers training for qualification in the requisite skills.
Safety requirements during commissioning include:
· The owner has received a confirmation of approval for use from the inspection
authorities.
· Conformity of the products with the approval according to EltVTR
(Tab. 5, page 56 "Appendix," page 60)
· Assembly according to the installation manual
· Testing of the unimpeded opening and closing function of the doors with the
escape route securing system deactivated
· Bolting of the doors after activation of the escape route securing system
· Allows the doors to be opened after actuation of the Emergency Open
push-button(s)
· The function must be tested with connected to fire alarm system
· The commissioning must be documented.
ASSA ABLOY Sicherheitstechnik GmbH
offers a test log book for this purpose.
Attention!
Propy damage from connection with USB devices:
The connection jacks on the
external display module 1386D00-DISP
and on the
Emergency Open module 1386D00
are
not USB jacks
and are only intended for connection of these two devices via a
standard USB cable A/B.
!
A
Set-up operation