We strongly recommend that 2-Wire mode 

is not used, specifically in PTO mode. Please 

see FAQ “What if I don’t have enough wires 

for 3-Wire Control” first to determine if this 

scenario will assist you.

If you must use 2-Wire Control, the Red & Green 

wires can be connected together and switched 

to control the lock.  This can also be achieved 

using the 9 – 12 adaptor (SP3782EL-251) 

which joins the red and green wires together 

and includes the new Lock Status monitor in 

series with the DPS reed switch and Deadlatch 

monitors. 

In 2-Wire PTO (Fail Secure) mode, the lock 

will receive no power when in the Locked 

state.  When the Access Control system sends 

an Unlock command to the Lock, it will send 

power to Unlock the door.  This power must 

be present for at least 5 seconds to enable the 

energy storage capabilities within the lock to 

regenerate so that the Lock can Re-Lock when 

the power has been removed.

3-Wire Control 

is when the Lock receives constant 

power on the Positive (Red) and Negative (Black) 

wires and the triggering control is achieved using 

the Control Wire (Green) which is a Positive (+) 

trigger.

3-Wire Control using a Separate Power Supply 

for the Control/Trigger

When using a different Power Supply for the 

Control Line (Green Wire) to that of the Power 

Supply to the Lock (Red & Black Wires), the 

Common/Negative line of both Power Supplies 

must be tied together.  This allows the Control 

wire to complete the circuit and actually trigger 

2-Wire Control

3-Wire and 2-Wire Control Diagrams

the Lock operation.  Failure to connect the two 

negatives will make the lock inoperable.

2-Wire Control

2-Wire Control is where the Lock receives a constant 
Negative (Black) and the Lock status changed using a 
Positive trigger on both the Positive (Red) and Control 
(Green) wires, which are tied together.
Lock Control must be switched on Positive ONLY.  As the 
Lock Body is grounded, if the Door Frame and Door are 
also Grounded and switching is performed through the 
Negative/Ground wire, the Lock will remain energised 
constantly.

Therefore, when configuring the Door Unlock 

functions in the Access Control system 

programming, do NOT enable a “Door Relock 

on Door Open” function.  This function will 

normally attempt to relock the Door as soon 

as the Door Position Input detects that the 

door has been opened after an Access Granted 

command.  This will then cut power to the lock, 

quite possibly within one second of the door 

being unlocked.  

The above scenario does not provide enough 

time for the Lock’s energy storage to be 

recharged and the Lock will have insufficient 

energy to relock.

Also ensure that the programmed ‘Door Unlock’ 

period is set to a minimum of 5 Seconds.  This 

will ensure that power is supplied for a sufficient 

amount of time for the Lock’s energy storage 

to be fully charged, allowing it to successfully 

perform its locking functions when the power 

has been removed.

Summary of Contents for Lockwood 3782EL

Page 1: ...www assaabloy co nz 1 3782EL trouble shooting guide Lockwood no worries www assaabloy co nz ...

Page 2: ... 8 Door position switch is not working 8 Lock status monitor is not working 9 LED is not active 9 LEDs turn off after 10 seconds 9 LED is not visible after fitting furniture 9 LED shines red briefly and then green after sending unlocking signal 9 There is no room for the cable when installing in a timber door 10 Can I leave a USB cable connected to the lock but power it via the main connector 10 I...

Page 3: ...ture improvements over the previous 3582 series including a far greater number of field selectable options inbuilt sounder LED indicators incorporated into the lock body and a motor drive design all best suited to 3 Wire configuration and operation As such please familiarise yourself with the Instruction Manual as installation and programming procedures are different to the previous Narrow Backset...

Page 4: ...t least two of the Monitored Outputs common outputs to salvage a spare wire for 3 Wire control Any or all of the following Commons on the Lock Outputs can be connected together 9 10 14 16 allowing for a minimum of 6 wires to achieve individual monitoring outputs for all functions being Door Position Deadlatch Lock Status REX Key Override Lock is not responding What if I don t have enough wires for...

Page 5: ... both Power Supplies must be tied together This allows the Control wire to complete the circuit and actually trigger 2 Wire Control 3 Wire and 2 Wire Control Diagrams the Lock operation Failure to connect the two negatives will make the lock inoperable 2 Wire Control 2 Wire Control is where the Lock receives a constant Negative Black and the Lock status changed using a Positive trigger on both the...

Page 6: ...a change of voltage as it is grounded through the door and will then remain in the powered state A positive 9 29VDC lock unlock signal must be supplied on the lock Wiring should be updated to ensure that the locking signal is switched on the positive side of the supply I am trying to set the lock up as double access 1 side PtL 1 side PtO but it is not working as expected If the lock is being used ...

Page 7: ...preparation may have a catch which is causing the hubs to not return fully If no furniture is fitted check correct voltage is being supplied to lock and power supply is able to deliver specified current Lock beeps three times on start up Triple beeping indicates an error with the setting switches Move the setting switches out of their current position and back to required setting taking care to en...

Page 8: ...handle is turned and closed when the handle is released REX will not operate when the lock is set to Escape Escape REX operates on the handle that is set to Escape only Confirm that the NO NC Normally Open Normally Closed switch on the side of the lock is set correctly and switch has travelled to selected side fully Door position switch is not working Confirm correct wires are being used by testin...

Page 9: ...owered in 2 wire mode red and green wires joined Wire lock in 3 wire configuration if continuous LED operation is needed LED shines red briefly and then green after sending unlocking signal The LED indicates the status of the lock and will only change to green once the lock has confirmed that it is definitely unlocked If the lock is being powered in 2 wire PtO this will result in the LED being off...

Page 10: ...an I leave a USB cable connected to the lock but power it via the main connector This is not recommended I have old LED furniture that I would like to re use is there an adaptor kit No new and improved 4800 lens furniture will need to be purchased I have an old 3582EL to replace is this lock interchangeable The lock is completely backwards compatible and a 9 12 pin adaptor SP3782EL 251 is availabl...

Page 11: ...ons for LED activation steps I am trying to lock one side of the lock but the cabling has not been installed how can I do this Set setting switches to required position PtO will leave the lock locked once power has been removed The lock can be powered via a micro USB connector connected to a power bank PC or mobile phone charger or it can be powered by the main connector with a 9 or 12V battery co...

Page 12: ...nd Ltd PO Box 100407 North Shore Auckland 0745 6 Armstrong Road Albany Auckland 0632 New Zealand Within New Zealand Tel 09 448 9188 Fax 0800 478 297 www assaabloy co nz Outside New Zealand Tel 64 9 448 9188 Fax 64 9 415 7889 www assaabloy co nz ...

Reviews: