background image

 

 

 

PN# 500-16900

 

 

Page 6 

Rev. D, 12/11 

3.4  USE OF THE “F” TERMINAL 
The F terminal on the power strip is not connected to 
anything.  It is a free terminal with either of two 

intended uses.  First, on some complicated 
installations, a large number of wires (generally DC 
negative) may require termination.  It can be 
convenient to run a jumper from the DC- terminal to 
the F terminal so that the large number of negative 

returns can be spread on to the two terminals.    
Second, some magnetic lock installations require 
interface with NC contacts controlled by the fire alarm 
system which will cut low voltage power 
immediately releasing the magnetic lock for 
safety
.  The connection to the fire alarm contacts is normally made in the power supply but if 

you are using a plug in power supply, you’ll want to make the connection on the DK-26 CPU 
board where you have terminals.  Using the example of a plug in AC transformer.  See the 
drawing to the right. 
 
3.5  ADDING OTHER LOCK CONTROL SWITCHES 
The drawings in Section 3.3 are valid for simple installations where the DK-26 is the only control 
device that can release the electric lock.  Often, however, additional control devices are called 
for.  The most common is some type of exit switch and this issue is covered in the next 
Section.  Sometimes other control switches are needed which are not appropriate for the REX 
input as use of this input triggers the timed release capability of the DK-26. 

 
A typical example would be a switch located centrally which would release the lock in response 
to an intercom call for example.  If the lock is fail safe, the switch will need to break power to 
the lock and if it’s fail secure, the switch will need to send power to the lock.  Figure 6 shows 
how to add external contacts for non timed remote release of the lock for both lock types. 
 

FIG. 6:  ADDING EXTERNAL CONTACTS FOR FAIL SAFE AND FAIL SECURE LOCKS 

NC1

C1

AC

IN

F

DC I

N

 /

O

UT

+

FAIL 
SAFE
LOCK

+

C

NC

MOV

FOR NON-TIMED REMOTE
RELEASE OF FAIL SAFE 
LOCK, PLACE NC CONTACTS
IN CIRCUIT AS SHOWN

NO1

C1

AC

IN

F

DC I

N

 /

O

UT

+

FAIL 
SECURE
LOCK

+

C

NO

MOV

FOR NON-TIMED REMOTE
RELEASE OF FAIL SECURE 
LOCK, PLACE NO CONTACTS
IN CIRCUIT AS SHOWN

 

3.6  THE REX FUNCTION 
Often, when the DK-26 is used, provision must be made to allow 
people to use the door freely from the inside.  If an electric strike 

is used, exit may be accomplished by purely mechanical means 
(turning the doorknob).  If, on the other hand, a solenoid 
operated or electromagnetic lock
 is used, free exit is only 
possible if a switch on the inside releases the lock
.  
Connection of this switch or switches is most easily accomplished by using the DK-26's REX 

input terminal (see Figure 2).  REX stands for Request To Exit.  When a normally open switch 
activates the REX terminal, the DK-26's control relay will open the lock for the amount of time 
programmed into the DK-26's timer.  The result is the same as if the DK-26 was used from the 
outside of the door.  The REX terminal is activated by being connected to the SRC (voltage 
source) terminal.  It will also activate if +12 or +24V is input to the terminal from the 

DK-26’s external power supply.  The drawing to the right shows the simplest connection to 
an external normally open momentary switch.  Any number of additional switches could be 
connected in parallel so that pressing any of them would activate the REX function. 

AC

IN

F

D

C I
N

 /

O

U

T

+

C

NC

TRANS-
FORMER

FIRE ALARM
CONTACTS

WHEN THE FIRE
ALARM CONTACTS
OPEN, ALL POWER
WILL BE REMOVED
FROM THE DOOR

 

SRC REX

AN N.O. SWITCH
CLOSING BETWEEN
"SRC" AND "REX"
CAUSES TIMED
RELEASE OF THE 
DOOR.

 

Summary of Contents for Securitron DK-26

Page 1: ...500 16900 Rev D 12 11 ASSA ABLOY the global leader in door opening solutions MODEL DK 26 DIGITAL KEYPAD SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS Securitron Magnalock Corp www securitron com Tel...

Page 2: ...PROGRAMMING Page 8 SECTION 4 2 KEYPAD CHANGEABLE PROGRAMMING Page 9 SECTION 4 2 1 CHANGING THE USER AND PROG CODE FROM KEYPAD Page 10 SECTION 4 2 2 ADDING MULTIPLE USER CODES Page 10 SECTION 4 3 MAST...

Page 3: ...eypad is pulled down firmly on to the screw A 3 8 10MM hole is then drilled for the cable After the cable has been pulled through the final screw secures the keypad to the wall Note finally that a bla...

Page 4: ...which could cause the microprocessor to malfunction The MOV should be spliced into the lock power wires as close to the lock as possible Some DC electric locks have internal kickback protection includ...

Page 5: ...om an AC transformer when the DK 26 is used Select a transformer of the same voltage as the lock 12 or 24 The CPU board converts the input AC to DC to operate the lock Make sure the capacity of the tr...

Page 6: ...DK 26 and the lock The DK 26 does not require regulated power but certain specialized electric locks do so follow the rule of matching the power supply to the requirements of the lock DC locks come i...

Page 7: ...to send power to the lock Figure 6 shows how to add external contacts for non timed remote release of the lock for both lock types FIG 6 ADDING EXTERNAL CONTACTS FOR FAIL SAFE AND FAIL SECURE LOCKS NC...

Page 8: ...while its normally open contacts activate the DK 26 In effect the lock is released twice Note that the NC contacts are placed in the circuit before the DK 26 s lock control relay This is to aid possi...

Page 9: ...programming in a situation where the end user is not likely to ever change the code or at least that changes would be rare Fixed programming can be used in lower security traffic control applications...

Page 10: ...ixed code programming 4 2 KEYPAD CHANGEABLE PROGRAMMING In this application two codes are programmed into the DK 26 The first called the Program code acts as a password which allows changing the User...

Page 11: ...ately by a new 2 7 digit User code Wait 5 seconds Note two red LED flashes for confirmation note rapid yellow flashing LED returns Press Bell key to terminate program mode or wait 30 seconds Re enter...

Page 12: ...code The unit could not be put into program mode from the keypad The DK 26 however avoids this problem by rejecting any code that is a subset of another code in memory It signals this rejection by sh...

Page 13: ...y by entering a User code and then secured all night by entering a User code again When you have enabled toggle mode activation of the REX input will successively energize and deenergize the lock cont...

Page 14: ...inary operation must be via one or more User codes see Section 4 2 for programming Program the Hard code as your duress code see Section 4 1 Put the unit in program mode and enter 7 5 You will see the...

Page 15: ...e simply by using the second pole of the lock control relay to shunt the door switch see Section 7 3 Generally you mount a Sonalert on the CPU board enclosure It will sound if the door is left open to...

Page 16: ...e terminals 7 3 ALARM SYSTEM SHUNTING The DK 26 s lock control relay is of the double pole double throw type Note that in all the other drawings in this manual we show only one of the poles being used...

Page 17: ...K 26 is often used with Securitron s Touch Sense Bar and magnetic lock The following drawing shows wiring for this particular configuration Note that the REX input is not used Since touching the bar o...

Page 18: ...timer Two digit codes must be entered from 01 to 99 seconds Default is 5 seconds Entering 00 sets toggle mode APPENDIX B TROUBLESHOOTING Note first that the DK 26 replaces older Securitron keypads the...

Page 19: ...nt through the PolySwitch trips it so that it clamps the current down to roughly 100 mA The PolySwitch will continue to clamp until all power is removed for about 5 seconds It is not enough to correct...

Page 20: ...ace the keypad for full operation PROBLEM Unit beeps when keys are pressed but does not accept programming If the problem occurs on initial installation usually it s caused by misunderstanding the pro...

Page 21: ...ry slot 45 You test the code by re entering 4 5 1 2 and the door opens because the sequence includes the real code 1 2 Later it will be noticed that the door is opening on 1 2 as this is such a simple...

Page 22: ...a fail secure lock is operated from the same supply as the DK 26 When the lock is energized it may draw too much power for the power source This reduces the voltage and these voltage swings can crash...

Page 23: ......

Reviews: