13 

500-17700, Rev D 

g. 

IF

 the above step does not solve the problem, 

THEN

 ENSURE that the ring terminal that connects the sensor to 

the handle itself has not come loose.

 

h.  CALL the factory if any of the above does not solve the problem, 

because the defect appears to be in the relay contacts and the 
sensor will have to be replaced.

 

The door remains released constantly 

NOTE:

 

The LED that comes on when the TSH senses a touch is most 

easily monitored if the plaque is removed. 

1. 

IF

 a click is heard when the handle is touched, 

AND

 the lock remains released, 

THEN

 REVIEW the wiring to be sure the sensor is correctly applied in 

the circuit, 

AND

 CORRECT, as necessary, 

AND

 RETEST. 

2. 

IF

 the LED is on constantly, 

OR

 a click is not heard when the TSH is touched, 

THEN

 ADJUST the sensitivity of the sensor (probably adjusted too 

high) by rotating the adjustment pot counterclockwise while not 
touching the handle, 

AND

 RETEST. 

3. 

IF

 the above steps do not solve the problem, 

AND

 the lock remains released, 

THEN

 ENSURE there is no "foreign object" creating a conductive 

path from the TSH to the door (e.g., metal blinds, water leak), 

AND

 CORRECT, as necessary, 

AND

 RETEST. 

NOTE:

 

Certain large electronic noise sources can "swamp" the sensor 

although this is rare.  Examples would include large radio or 
radar transmitters in the building or a high voltage neon sign 
mounted within a few feet of the door. 

4. 

IF

 a noise induced problem is suspected, 

THEN

 CALL the factory for assistance. 

Summary of Contents for Securitron EL-TSH-BK

Page 1: ...1 500 17700 Rev D Model TSH Touch Sense Handle Installation and Operation Instructions ...

Page 2: ...o the Door 5 Connect the Electrical Within the Plastic Base 5 Mount the Handle to the Plastic Base 6 Connect the Electrical Wiring and Power Supply 6 Adjust and Test the Sensitivity 8 Test and Use the Redundant Backup Switch 10 Install the Plaque 10 Select the Electric Lock 10 Replace the Sensor 11 Operational Security Considerations 11 Troubleshooting 12 MagnaCare Lifetime Replacement Warranty 14...

Page 3: ... In the unlikely event of sensor failure a push switch is mounted on the plastic base Depressing the switch has the same effect as activating the sensor by touch and therefore represents built in safety redundancy The TSH cannot be used outside in rain conditions As the TSH is normally used to allow egress on an electrically secured door make sure that you are complying with applicable building co...

Page 4: ...completely through the door NOTE The TSH may be mounted with wood screws not furnished It is recommended that 1 3 4 14 wood screws with a hex pan oval or round head be used for mounting 3 For a solid wood door DRILL two 3 16 5 mm diameter holes to a depth of 1 1 4 32 mm NOTE 1 The TSH connects to its power source and to the devices it controls using a six conductor cable with push on connector sup...

Page 5: ...he Blind Nuts in a Metal Door d PLACE a tooth washer under the head of each screw and MOUNT the plastic base e TIGHTEN the cap screw but DO NOT OVERTIGHTEN Figure 1 Collapsing the Blind Nuts in a Metal Door Connect the Electrical Within the Plastic Base NOTE Electrical connections with the plastic base must be made before the handle is attached to the base 1 ROUTE the cable connector across the ci...

Page 6: ... Lock and Figure 4 TSH Double Break Wiring show a generic use of the TSH with any type magnetic lock and power supply NOTE 2 When using all Securitron products the installation is simple It should be noted that for any Securitron Magnalock the red wire denotes the input and the black wire denotes the input Also the MOV does not need to be installed with any Securitron Magnalock 1 CONNECT the elect...

Page 7: ... Power White Relay Common Pole 1 Green Relay Normally Closed Pole 1 Blue Relay Common Pole 2 Orange Relay Normally Closed Pole 2 Figure 3 TSH Wiring for Fail Safe Electric Lock Figure 4 TSH Double Break Wiring 2 CONNECT the power supply outputs to the rest of the system as shown above ...

Page 8: ...THEN CONNECT one 0 01 mF capacitor between power supply and earth ground and CONNECT a second 0 01 mF capacitor between power supply and earth ground see Figure 5 Connecting Capacitors to a Switching Power Supply Figure 5 Connecting Capacitors to a Switching Power Supply 2 PERFORM the following test to make sure a problem does not exist after the installation is complete a TURN UP the sensitivity ...

Page 9: ...he sensitivity NOTE 1 The sensor board has a potentiometer which is accessible through a pot access hole from the top of the aluminum handle before the plaque has been installed see Figure 2 The potentiometer increases sensitivity when turned clockwise and decreases it when turned counterclockwise An LED on the sensor circuit board also visible through an access hole in the aluminum handle see Fig...

Page 10: ...ic preference NOTE 2 A choice of colors is provided for the included screws to match the selected plaque color 1 INSTALL a plastic plaque in the slot in the aluminum handle to cover up the mounting holes and access holes to the circuit board after the wiring is complete Select the Electric Lock NOTE 1 The TSH allows silent and immediate egress without the mechanical action of traditional exit devi...

Page 11: ...is a common problem with other interior release devices For instance if a panic bar with switch is used it is possible to trip it from the outside if a would be intruder can introduce a coat hanger in between the door and frame Aluminum frame glass doors tend to allow this more than other types Similarly microwave detectors used on the inside can sometimes be activated from the outside if the door...

Page 12: ...hen the TSH is touched b Alternately REMOVE the plaque and MONITOR the LED which comes on when the TSH senses touch c IF a click is not heard OR the LED does not come on THEN TRY the backup switch NOTE A door that does not release from a touch of the TSH and from a push on the backup switch shows that there is most likely a fault in the overall installation wiring d IF the door does not open after...

Page 13: ...the circuit AND CORRECT as necessary AND RETEST 2 IF the LED is on constantly OR a click is not heard when the TSH is touched THEN ADJUST the sensitivity of the sensor probably adjusted too high by rotating the adjustment pot counterclockwise while not touching the handle AND RETEST 3 IF the above steps do not solve the problem AND the lock remains released THEN ENSURE there is no foreign object c...

Page 14: ...t by next day air freight at no cost to the customer within 24 hours of SECURITRON s receipt of the product from customer If the customer has an account with SECURITRON or a valid credit card the customer may order an advance replacement product whereby SECURITRON will charge the customer s account for the price of the product plus next day air freight and will credit back to the customer the full...

Page 15: ...or consequential damages arising from any defect in or malfunction of its products SECURITRON does not assume any responsibility for damage or injury to person or property due to improper care storage handling abuse misuse or an act of God EXCEPT AS STATED ABOVE SECURITRON MAKES NO WARRANTIES EITHER EXPRESS OR IMPLIED AS TO ANY MATTER WHATSOEVER INCLUDING WITHOUT LIMITATION THE CONDITION OF ITS PR...

Page 16: ...44 1 800 MAGLOCK 1 800 624 5625 Mon Fri 6 00am 4 00pm PDT www securitron com 2015 Hanchett Entry Systems Inc an ASSA ABLOY Group Company ASSA ABLOY is the global leader in door opening solutions dedicated to satisfying end user needs for security safety and convenience ...

Reviews: