background image

of 8

Latch Status Sensing 

The Securitron UnLatch includes a latch status 

sensing feature. When the door is closed and the 

door latch has engaged the Securitron UnLatch 

(specifically the springlatch plunger has been 

pushed in by the door latch), the Securitron UnLatch 

will 

report this secure condition

 by outputting a 

closed circuit condition between the white (COM) 

and green wires (see the drawing to the right). 

When the door is not securely latched,

 the closure 

will be between the white and blue wires. This dry SPDT 

output can carry 

1 Amp at 30 VDC maximum

. This signal 

is normally connected to the building alarm system and it 

provides superior information compared to conventional 

door contacts which show only that the door is closed, 

not whether it is latched.  Note that the Securitron 

UnLatch’s ability to report on the latched status of the 

door 

depends on it receiving constant power

. Any time 

power is cut to the Securitron UnLatch, it will report 

the door as secure regardless of whether it is latched or 

not. The Securitron UnLatch uses the information as to 

whether the door is latched or not for a second purpose. 

The Securitron UnLatch will not operate unless 

the latch is in the secure position

 (the springlatch 

plunger is pushed in). The reason for this is to 

avoid a potential jam condition. If the door had 

not fully closed, the springlatch could be adjacent 

to the dead latch plunger and the dead latch pin 

would be resting on the metal “strike” casing of 

the Securitron UnLatch. In this condition, if the 

Securitron UnLatch was allowed to operate, the dead 

latch plunger would attempt to push the springlatch 

and it would be unable to do so because the dead 

latch pin would be pushed in by the metal casing 

of the Securitron UnLatch. The motor would jam. 
The Securitron UnLatch senses any motor jam 

condition and shuts itself down for that cycle 

but it is better not to operate at all unless the 

door is latched. Operationally, the door can be 

opened anyway (it is not latched) so there is 

no benefit to the end user from the Securitron 

UnLatch operating unless the door is latched.

Wire Gauge Sizing 

If the power supply is some distance from the lock, 

voltage will be lost (dropped) in the connecting wires 

so that the Securitron UnLatch will not receive full 

voltage. The amount of voltage that is dropped in 

the wires depends on the resistance of the “round 

trip” wire run compared to the resistance of the 

Securitron UnLatch. The issue is complicated by the 

fact that the resistance of the Securitron UnLatch is 

35 Ohms at 12 VDC or 120 Ohms at 24 VDC when it 

is operating (the motor is moving) but the resistance 

drops as low as 4 Ohms at 12 VDC or 16 Ohms at 24 

VDC for 100 milliseconds just as the motor starts. 

If the unit is denied full voltage

 during this motor start 

period, it will operate but with less torque so it will not 

release the latch as crisply when the latch has pre-load 

on it. Selecting thick wires to power the Securitron 

UnLatch will maintain strong torque even during start up. 

The following table shows distances from the 

Securitron UnLatch to the power source and calls out 

the wire gauge needed to fully maintain torque. 

NOTE:

 that if your installation requires the 

power source to be more distant or has other 

complications, the factory can assist you. 

PRODUCT

DISTANCE (ONE WAY)

50 FT. [15 M]

100 FT. [30 M]

200 FT. [60 M]

Wire Gauge for 

Securitron UNL-12

16

14

12

Wire Gauge for 

Securitron UNL-24

22

20

18

GREEN

NC

NO

COM

BLUE

WHITE

Summary of Contents for Securitron UnLatch

Page 1: ... type which is also called tubular Examples of latch types on which the Securitron UnLatch will not function include many panic bar latches and rim latches rim latches are on the surface of the door rather than being mortised into the middle of the door The Securitron UnLatch also will not function on mortise latches These are heavy duty rectangular units similar in appearance to warning above Aft...

Page 2: ... to fit the Securitron UnLatch into the frame vacuum out any concrete dust and metal shavings these can work their way into the Securitron UnLatch mechanism and cause problems 2 3 4 ANSI strike In the case of a 2 3 4 ANSI strike you will be using two new holes which are separated more widely to mount the Securitron UnLatch You will also have to perform two chiseling operations You will have to chi...

Page 3: ...agram 5 to cause the door to close earlier If the amount of slack or rattling is less than 1 16 1 8 You have a tight door and the ability of the door to close and latch reliably is in question To adjust for this 1 CHECK to see if the stop has silencers on it These are cylindrical rubber bumpers which quiet the noise of a closing door but also have the effect of making the door close earlier 2 REMO...

Page 4: ...atch pin rests on the deadlatch plunger which pushes in the deadlatch pin This maintains the latch in the secure position and makes full use of the deadlatching function When the Securitron UnLatch operates the trigger wire connects to the V wire the deadlatch plunger retracts into the body of the Securitron UnLatch which allows the deadlatch pin to move out Then both plungers simultaneously push ...

Page 5: ... bridge rectifier combination can be as high as forty volts the diodes are required to drop the peak voltage into the operable range for the UNL 24 Diagram 10 notes installation placement of the Zener diodes NOTE The addition of the Zener diodes is only required when using the Securitron UNL 24 with 24 VAC transformer and bridge rectifier When using the Securitron UNL 12 with 12 VAC transformer an...

Page 6: ... would be unable to do so because the dead latch pin would be pushed in by the metal casing of the Securitron UnLatch The motor would jam The Securitron UnLatch senses any motor jam condition and shuts itself down for that cycle but it is better not to operate at all unless the door is latched Operationally the door can be opened anyway it is not latched so there is no benefit to the end user from...

Page 7: ...rocessor will sharply drop and this can crash the microprocessor A crash can also occur as a random event but this is unusual There are two recovery methods that may be used to recover the unit s operation The first technique is a simple reset achieved by cycling power to the unit Remove power V from the unit s red wire momentarily After power is reapplied the unit may reset and begin normal opera...

Page 8: ...sionofHanchettEntrySystems Inc is prohibited 500 18300_5 Warranty For information on warranty coverage and replacement options please visit assaabloyesh com warranty Template 4 7 8 123 8 mm 4 1 8 104 8 mm 1 1 4 107 95 CENTER LINE Horizontal Alignment Arrows see Diagram 4 Dotted line shows area to chisel out 1 3 4 44 45mm deep for installation in wood frame DO NOT photo copy template Dimensions wil...

Reviews: