background image

 

Securitron Magnalock Corp. 

www.securitron.com 

ASSA ABLOY, the global leader 

 

 Tel 

800.624.5625 

techsupport@securitron.com 

in door opening solutions

 

 

 

 

 

 

 
 

 

© Copyright, 2011, all rights reserved 

 

PN# 500-18000

 

 

Page 1  

Rev. D, 10/11 

 

SECURITRON MODEL XMS EXIT MOTION SENSOR 

INSTALLATION AND OPERATING INSTRUCTIONS 

 

1.  DESCRIPTION 
The XMS is a passive infrared motion detector specifically designed to release a magnetic lock 

from the inside for free egress.  Unlike burglar alarm type detectors, the XMSìhas special 
features appropriate to this use.  The lock control function is fail safe so that the magnetic 
lock will safely release if power is cut to the detector.  A relay is also present to send a REX 
(request to exit) signal to an access control system (if one is present) and therefore shunt an 
alarm report.  A time extension feature avoids the problem of the unit resetting if a person 

momentarily stops moving just before exit.  Tight control of the exit detection pattern allows 
maximum security from the outside and avoidance of inadvertent activation from the inside. 
 
Since egress from a magnetically locked door can be a safety issue, make sure you are 
complying with local building codes.  Contact your building and/or fire prevention 

department. 
 
2.  PHYSICAL INSTALLATION 
2.1  PLACEMENT OF THE UNIT 
The XMS is intended for indoor use only.  It is positioned with respect to the inside of the door 
so that its detection pattern will “see” a person approaching the door while maintaining good 

security from the outside.  There are different options as to where the unit is placed depending 
on variables in the application. 
 

FIG. 1:  PLACEMENT OPTIONS FOR THE SENSOR 

FOR TRAFFIC CONTROL
APPLICATIONS, MOUNT THE
SENSOR IN THE CENTER OF
THE DOOR WITH THE
PATTERN AS SHOWN

FOR SECURITY
APPLICATIONS, THE
PATTERN SHOULD SWEEP
ACROSS THE EXIT DEVICE
BUT MISS THE BOTTOM OF
THE DOOR.  THE SENSOR IS
POSITIONED BEYOND THE
HINGE SIDE OF THE DOOR

WHEN A DOORKNOB IS
PRESENT IN A SECURITY
APPLICATION, THE
PATTERN CAN BE MADE
MORE NARROW

THE SENSOR CAN BE
POSITIONED AT THE
SIDE FOR SECURITY
APPLICATIONS ON
DOORS AT THE END
OF CORRIDORS

 

The simplest method of placing the unit is for traffic control applications.  A traffic control 

application is one where you do not expect any attempt at breaking in from the outside.  The 

Summary of Contents for SECURITRON XMS

Page 1: ...he inside Since egress from a magnetically locked door can be a safety issue make sure you are complying with local building codes Contact your building and or fire prevention department 2 PHYSICAL IN...

Page 2: ...nd loosen it This permits you to remove the cover The appearance of the interior is shown in Figure 2 Note that the interior electronics is mounted on a rotating barrel which is locked by the Barrel L...

Page 3: ...ALARM SYSTEM ON DOOR DOOR SWITCH TO ALARM PANEL DOOR SWITCH TO ALARM PANEL ALARM SIGNAL WHICH IS CLOSED WHEN DOOR IS CLOSED OPENS TO ALARM ALARM SIGNAL WHICH IS OPEN WHEN DOOR IS CLOSED CLOSES TO ALAR...

Page 4: ...SEE SECTION 5 IN D VICE C1 NC1 NO1 3 5 ACCESS CONTROLLED EGRESS DOOR In some jurisdictions the combination of a magnetic lock access control system and exit detector such as the XMS can be considered...

Page 5: ...the lock control transistor You need to understand how the unit s control outputs operate in a detection event In the rest condition green LED on no detection the lock control transistor is conductin...

Page 6: ...our second timing feature of the lock control relay can be altered by changing jumper settings see Section 5 but the REX relay always operates 50 milliseconds before and one second after the lock cont...

Page 7: ...eight second setting is rarely used unless there is strong concern for maximum time being allocated for egress even when movement is not maintained The problem with an eight second trailing edge dela...

Page 8: ...th the aiming screw settings you must also finalize the degree of barrel assembly rotation You don t want the unit seeing the surface of the door itself as this can lead to false detection so in the c...

Reviews: