DRV-28 inverter
s Basic operartion instructions
-100-
0
1
2
3
4
5
.
.
.
.
29
30
P06.01
P06.03
P06.04
P06.02
T delay
T delay
T delay
T delay
0
1
P06.05 output polarity
selection
(
Default value: 0
)
(
Default value: 0
)
(
Default value: 1
)
(
Default value: 5
)
P06.00
HDO
input type
0
1
0
1
0
1
delay
0
1
-1
-1
-1
-1
P17.12
Digital input
terminal state
P07.40
Digital output
terminal state
of current fault
Fault
?
Fault
Run
Y
BIT0
HDO
BIT1
ROI
BIT2
RO2
BIT3
P06.05, P17.12, P07.40 display
P06.00
0: Open collector high-
speed pulse output
1: Open collector output
P06.07
P06.09
P06.11
P06.13
Y
RO2
ROI
HDO
Digital switch-off delay
Digital output selection
T delay
T delay
T delay
T delay
delay
P06.06
P06.08
P06.10
P06.12
Digital switch-on delay
The table below lists the options for the above four function parameters, and users are allowed to
select the same output terminal functions repetitively.
Set
value
Function
Description
0
Invalid
Output terminal has no function
1
In running
Output ON signal when there is frequency output during
running
2
In forward running
Output ON signal when there is frequency output during
forward running
3
In reverse running
Output ON signal when there is frequency output during
reverse running
4
In jogging
Output ON signal when there is frequency output during
jogging
5
Inverter fault
Output ON signal when inverter fault occurred
6
Frequency level detection
FDT1
Refer to P08.32 and P08.33
7
Frequency level detection
FDT2
Refer to P08.34 and P08.35
8
Frequency reached
Refer to P08.36
9
Running in zero speed
Output ON signal when the inverter output frequency and
reference frequency are both zero.
10
Reach upper limit
frequency
Output ON signal when the running frequency reaches
upper limit frequency
11
Reach lower limit
frequency
Output ON signal when the running frequency reached
lower limit frequency
12
Ready to run
Main circuit and control circuit powers are established,
the protection functions do not act; when the inverter is
ready to run, output ON signal.
13
In pre-exciting
Output ON signal during pre-exciting of the inverter
14
Overload pre-alarm
Output ON signal after the pre-alarm time elapsed based