DRV-28 inverter
s Function parameter list
-158-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
Reverse running
Note: For dual-line running mode, when
FWD/REV terminal is valid, if the inverter stops
due to stop command given by other sources, it
will not run again after the stop command
disappears even if the control terminals
FWD/REV are still valid. To make the inverter run
again, users need to trigger FWD/REV again, eg,
PLC single-cycle stop, fixed-length stop, and
valid STOP/RST stop during terminal control.
(see P07.04)
P05.12
S1 terminal
switch-on delay
These function codes define corresponding delay of
the programmable input terminals during level
variation from switch-on to switch-off .
Si electrical level
Si valid
invalid
invalid
Switcn-on
delay
Switcn-off
delay
valid
Setting range: 0.000–50.000s
Note:
After a virtual terminal is enabled, the state of
the terminal can be changed only in communication
mode. The communication address is 0x200A.
0.000s
○
P05.13
S1 terminal
switch-off delay
0.000s
○
P05.14
S2 terminal
switch-on delay
0.000s
○
P05.15
S2 terminal
switch-off delay
0.000s
○
P05.16
S3 terminal
switch-on delay
0.000s
○
P05.17
S3 terminal
switch-off delay
0.000s
○
P05.18
S4 terminal
switch-on delay
0.000s
○
P05.19
S4 terminal
switch-off delay
0.000s
○
P05.20
HDIA terminal
switch-on delay
0.000s
○
P05.21
HDIA terminal
switch-off delay
0.000s
○
P05.22
HDIB terminal
switch-on delay
0.000s
○
P05.23
HDIB terminal
switch-off delay
0.000s
○
P05.24
Lower limit value
of AI1
These function codes define the relation between
analog input voltage and corresponding set value of
analog input. When the analog input voltage
0.00V
○
P05.25
Corresponding
0.0%
○