DRV-28 inverter
s Function parameter list
-173-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
output frequency)
Setting range of P08.35: 0.0–100.0% (FDT2 level)
P08.36
Detection value
for frequency
arrival
When the output frequency is within the positive
/negative detection range of the set frequency, the
multi-function digital output terminal outputs
"frequency arrival" signal as shown below.
Y,
RO1, RO2
Output frequency
Set
frequency
Detection amplitude
Time t
Time t
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
0.00Hz
○
P08.37
Enable/disable
energy-
consumption
brake
0: Disable energy-consumption
1: Enable energy-consumption
1
○
P08.38
Energy-
consumption
brake threshold
voltage
Set the starting bus voltage of energy-consumption
brake, adjust this value properly can brake the load
effectively. The default value will change with the
change of voltage class.
Setting range: 200.0–2000.0V
230V
voltage:
380.0V;
400V
voltage:
700.0V;
660V
voltage:
1120.0V
○
P08.39
Running mode of
cooling fan
0: Common running mode
1: The fan keeps running after power up
0
○
P08.40
PWM selection
0x0000–0x2121
Ones: PWM mode
0: 3PH modulation and 2-phase modulation
1: 3PH modulation
Tens: PWM low-speed carrier limit
0: Limit low-speed carrier to 2K