AS64 series AC servo drive Function codes
-229-
R0.47
Speed observer
feedback
Setting range
Accuracy
Unit
-9999.9
–9999.9
0.1
r/min
This parameter displays the feedback speed from the speed observer.
R0.47
Data size
32bit
Data format
DEC
Modbus address
4098, 4099
CANopen address
0x302F, 0x00
R0.48
Torque from
disturbance
observer
Setting range
Accuracy
Unit
-1000.0–1000.0
0.1
%
This parameter displays the compensation torque from the disturbance observer.
R0.48
Data size
32bit
Data format
DEC
Modbus address
4100, 4101
CANopen address
0x3030, 0x00
R0.49
Fully-closed loop
vibration suppressor
compensation
Setting range
Accuracy
Unit
-9999.9
–9999.9
0.1
r/min
This parameter displays the compensation from the fully-closed loop vibration suppressor.
R0.49
Data size
32bit
Data format
DEC
Modbus address
4102, 4103
CANopen address
0x3031, 0x00
R0.51
Real-time load inertia
ratio
Setting range
Accuracy
Unit
0–10000
1
%
This parameter displays the load inertia ratio observed in real time.
R0.51
Data size
16bit
Data format
DEC
Modbus address
4106, 4107
CANopen address
0x3033, 0x00
R0.52
Accumulated grating
ruler (or encoder 2)
position feedback (32-
bit)
Setting range
Accuracy
Unit
-(2
31
-1)–(2
31
-1)
1
pulse
This parameter accumulates and displays the 32-bit absolute position feedback from the grating
ruler (or second encoder). It can be read quickly. If the feedback exceeds 32 bits, it is replaced by
R0.57.
R0.52
Data size
32bit
Data format
DEC
Modbus address
4108, 4109
CANopen address
0x3034, 0x00