© ASTRALPOOL 2008. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Page 54 of 69
ENGLISH
6.2 TEMPERATURE
CONTROL
The decrease of temperature below 21 ° C will cause the safety evaporation driver to cut
operation of the compressor, which will remain unpowered until the automatic reset (Ambient
temperature above 21 º C).
This reset will occur when the differential temperature is reached. During this time the fan is
running.
It is not appropriate for the machine to work continuously in these conditions.
We recommend you to unpower the machine when you're not going to use the
equipment for prolonged time periods or in conditions of low temperature (below 21 º C).
7 OPERATING
MODES
The equipment has two operating modes, user selectable:
OPERATING MODE #1: FAN ALWAYS ON (recommended)
In this operating mode, the fan will always be on if the equipment main switch is ON, even if the
enclosure to be regulated is within humidity and/or temperature set points.
This way, a valious air flow is achieved and therefore, more accurate temperature and humidity
readings will be available.
OPERATING MODE #2: INTERMITTENT FAN
In this operating mode, the fan will only be on if the equipment detects that air conditions are
outside set points and therefore, frigorific circuit and/or air heating system will be powered on.
This way, energetic saving are achieved althought temperature and humidity measures are less
accurate.
Switching between this two
modes is performed through the
switch in the lateral left of the
equipment.
The equipment is provided
configured on operating mode
#1, fan always on.
Figura 11: Swhitch for operating mode change.