background image

www.Astria.US.com

126688-01A

7

DETERMINING FRESH-AIR FLOW 

FOR FIREBOX LOCATION

Determining if You Have a Confined or 

Unconfined Space

Use this work sheet to determine if you have 

a confined or unconfined space.

Space:

 Includes the room in which you will 

install  appliance  plus  any  adjoining  rooms 

with doorless passageways or ventilation grills 

between the rooms.

1.  Determine the volume of the space (length 

x width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example:

 Space size 22 ft. (length) x 18 ft. 

(width) x 8 ft. (ceiling height) = 3168 cu. ft. 

(volume of space)

 

If  additional  ventilation  to  adjoining  room 

is supplied with grills or openings, add the 

volume of these rooms to the total volume 

of the space.

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can sup-

port.

 

 ________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

 

Example:

 3168 cu. ft. (volume of space) x 20 

= 63,360 (maximum Btu/Hr the space can 

support)

3.  Add the Btu/Hr of all fuel burning appliances 

in the space.

 

Gas water appliance*   __________ Btu/Hr

 

Gas furnace 

 __________ Btu/Hr

 

Vented gas appliance   __________ Btu/Hr

 

Gas fireplace logs 

 __________ Btu/Hr

 

Other gas appliances* + _________ Btu/Hr

 Total 

= _________ Btu/Hr

 

* Do not include direct-vent gas appliances. 

Direct-vent draws combustion air from the 

outdoors and vents to the outdoors.

 

Example:

 

Gas water appliance   __________ Btu/Hr

 

Gas firebox logs 

+ _________ Btu/Hr

 Total 

= _________ Btu/Hr

AIR FOR COMBUSTION AND VENTILATION

Continued

  40,000
  39,000
  79,000

4.  Compare the maximum Btu/Hr the space 

can support with the actual amount of Btu/

Hr used.

 

 _______ Btu/Hr (maximum the space can 

support)

 

 _______ Btu/Hr (actual amount of Btu/Hr 

used)

 

Example:

  63,360  Btu/Hr  (maximum  the 

space can support)

 

 

79,000 Btu/Hr (actual amount of 

Btu/Hr used)

The space in the above example is a confined 

space because the actual Btu/Hr used is more 

than the maximum Btu/Hr the space can sup-

port. You  must  provide  additional  fresh  air. 

Your options are as follows:
A.  Rework  work  sheet,  adding  the  space 

of an adjoining room. If the extra space 

provides  an  unconfined  space,  remove 

door to adjoining room or add ventilation 

grills between rooms. See 

Ventilation Air 

from Inside Building

, page 8.

B.  Vent room directly to the outdoors. See 

Ventilation Air from Outdoors

, page 8.

C.  Install a lower Btu/Hr gas log appliance, if 

lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the 

maximum Btu/Hr the space can support, the 

space is an unconfined space. You will need 

no additional fresh air ventilation.

 WARNING: If the area in which 

the appliance may be operated 

does not meet the required vol-

ume for indoor combustion air, 

combustion and ventilation air 

shall be provided by one of 

the methods described in the 

National Fuel Gas Code, ANSI 

Z223.1/NFPA 54, 

the

 Internation-

al Fuel Gas Code,

 or applicable 

local codes.

Summary of Contents for TaurusPFZ

Page 1: ...xplosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas s...

Page 2: ...Ceiling fans can create drafts that alter burner flame patterns Altered burner patterns can cause sooting SAFETY This appliance may be installed in an aftermarket permanently located manufactured mobile home where not prohibited by local codes Aftermarket Completion of sale not for purpose of resale from the manufacturer This firebox has been tested under Z21 91b 2007 for use with approved ANSI Z2...

Page 3: ... cause pilot outage 12 Do not use the firebox if it has been un der water due to the shock hazard that could result with the blower accessary if installed in place 13 Provide adequate clearances around air openings Due to high temperatures the appliance should be located out oftrafficandawayfromfurniture and draperies Do not place clothing or other flammable material on or near the appliance Never...

Page 4: ...re you bought firebox 3 Check appliance for any shipping damage If appliance is damaged call INNOVATIVE HEARTH PRODUCTS at 1 800 655 2008 for replacement parts before returning to dealer NOTICE The firebox identifica tionlabel includingmodelnum ber serial number clearances etc islocateddirectlyabovethe brick liner and under the heat shield See Figure 20 page 16 PRODUCT FEATURES OPERATION This fire...

Page 5: ...box will be located Allow for wall and ceiling clearances see Installa tion Clearances page 9 2 Everything needed to complete installation 3 This model CANNOT be installed in a bedroom or bathroom 4 Proper air for combustion and ventilation 5 Consider a location where heat output would not be affected by drafts air condi tion ducts windows or doors 6 A location that minimizes modifications on exis...

Page 6: ...y provide enough fresh air for combustion and ventilation However in buildings of un usually tight construction you must provide additional fresh air Unusually tight construction is defined as construction where a walls and ceilings exposed to the out side atmosphere have a continuous water vapor retarder with a rating of one perm 6 x 10 11 kg per pa sec m2 or less with openings gasketed or sealed...

Page 7: ... vents to the outdoors Example Gas water appliance ___________ Btu Hr Gas firebox logs __________ Btu Hr Total __________ Btu Hr AIR FOR COMBUSTION AND VENTILATION Continued 40 000 39 000 79 000 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used ________ Btu Hr maximum the space can support ________ Btu Hr actual amount of Btu Hr used Example 63 360 Btu Hr max...

Page 8: ... 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors or spaces open to the outdoors These spaces include at tics and crawl spaces Follow the National Fuel Gas Code ANS Z223 1 NFPA 54 Air for Combustion and Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermo ...

Page 9: ... provide greater clearances from floor ceiling and adjoining wall Carefully follow the instructions below This will ensure safe installation Minimum Wall and Ceiling Clearances A Clearances from edge of liner to any combustible wall should not be less than 8 see Figure 5 B Clearances from top of firebox opening to the ceiling should not be less than 42 INSTALLATION Continued C When the firebox is ...

Page 10: ... installation of this firebox involves installing firebox into a framed in enclosure This makes the front of firebox flush with wall If installing a mantel above the firebox you must follow the clearances shown in Figure 7 Follow the instructions below to install the Figure 7 Minimum Mantel Clearances for Built In Installation 4 Min 43 3 4 Min 36 Min to Facing Wall 22 3 4 Min Facing Wall Wallboard...

Page 11: ...ouvered slots on the front of the firebox WARNING Use only non combustible mortar or adhe siveswhenoverlappingthefront facing with noncombustible facing material WARNING Do not fill the spaces around the firebox with insulation or other materials WARNING Framing may be placed or rest against fireplace spacer however framing must never be notched WARNING Do not alter cut or modify fireplace spacers...

Page 12: ...ay be run from the regulator to the incoming 1 2 NPT black iron gas line You may also route the incoming 1 2 NPT black iron gas line directly to the appliance regulator Remove the gas line cover plate from the vent free firebox s outer surround and route Figure 11 Installing Gas Line and Manual Shutoff Valve Manual Shutoff Valve is Located Under Firebox Floor on Either Side Gas Line Installed Thro...

Page 13: ...sures in excess of 1 2 psig 3 5 kPa The appliance must be isolated from the gas supply piping system by closing manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Figure 15 Locating Electrical Connection and Gas Connection on Either Side of Fireplace HARD WIRING FIREBOX This model can be hard wired to the duple...

Page 14: ...ating air passageways of the appliance be kept clean WARNING Children and adults should be alerted to the hazardsofhighsurfacetempera tures and to stay away to avoid burnsorclothingignition Young children should be carefully supervised when they are in the same room as the appliance For lighting and operating this vent free firebox please refer to the vent free gas logs manufacturer s instruction ...

Page 15: ...ioning purchase date Usually we will ask you to return the part to the factory TECHNICAL SERVICE You may have further questions about installa tion operation or troubleshooting If so contact INNOVATIVE HEARTH PRODUCTS at 1 800 655 2008 Whencallingpleasehaveyourmodel and serial numbers of your appliance ready You can also visit the INNOVATIVE HEARTH PRODUCTS web site at www IHP US com ACCESSORY Pur...

Page 16: ... com 126688 01A 16 PARTS MODEL TAURUSPFZ2 These items are used on both sides of fireplace 8 15 17 17 17 7 1 7 2 7 3 2 17 11 17 17 12 6 16 13 10 5 17 17 15 16 4 16 16 6 16 15 17 17 18 Typ Typ Typ 8 17 17 9 14 16 1 3 ...

Page 17: ...acer 4 5 26731 Deflector Hood 2 6 26740 Nailing Flange 12 7 1 02013 Side Refractory Brick Liner 1 7 2 02014 Bottom Refractory Brick Liner 1 7 3 02036 Bottom Refractory Brick Liner 1 8 24007 Side Refractory Retainer 2 9 12125 Screen 4 10 26752 Extruded Louver 2 11 26733 Lower Door Panel 2 12 14200 Receptacle 1 13 21171 Access Hole Cover 3 14 12126 Screen 1 15 26771 Extruded Louver End 1 16 11164 Sc...

Page 18: ... flood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected to normal use The Product is designed to burn either natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive tempera...

Page 19: ...IS WARRANTY Model located on product or identification tag ______________________________ Serial No located on product or identification tag ___________________________ Date Purchased ___________________________ Keep receipt for warranty verification ...

Page 20: ...126688 01 Rev A 02 14 1508 Elm Hill Pike Suite 108 Nashville TN 37210 1 800 655 2008 www IHP US com P126688 01 ...

Reviews: