Therefore the main advantages of the use of a 12 pulses rectifier are:
•
Lowest harmonic content of the AC input current
•
Lowest ripple on the DC output voltage
•
Better operating conditions for the AC supply cables
•
Better operating conditions for a possible diesel generator
Picture 31 – Rectifier 12P with galvanic isolation
6.3
IP31 PROTECTION DEGREE
An increased protection degree is available on request instead of the standard IP20. In this
case an additional roof is added to guarantee the protection against the falling of drops of
water and additional grids, with smaller holes, are installed behind the existing openings.
6.4 SPECIAL
PAINT
Different colours are available on request and with an additional cost. The special paint
can be requested according to the RAL colours standard.
6.5
FUSED SWITCH FOR THE BATTERY
The fused switch for the battery is a switch with integrated fuses and it is used to separate
the UPS from the external battery. The fused switch is necessary in installations where the
batteries are installed in a dedicated battery room, so a sectioning device is necessary
between the UPS and the battery.