30
*
4600VA with VDE-AR-N 4105 , CEI0-21
**
23A with output power 4600W
***
0.95leading…0.95lagging with VDE-AR-N 4105
0.95leading…0.95lagging with CEI 0-21 (System power less than 6KW)
0.9leading…0.9lagging with CEI 0-21 (System power larger than 6KW)
Nominal AC output power
Max. AC apparent power
Nominal output current
Max. output current
AC nominal voltage;
range
AC grid frequency;
range
Phase factor at rate power
Displacement power factor,
configurable ***
THDI
AC connection
3600W
3600VA
15.6A
18A
220V / 230V / 240V
180Vac - 280Vac
50Hz,60Hz;±5Hz
1
0.9leading…
0.9lagging
<3%
Single phase
4200W
4200VA
18.5A
21A
220V / 230V / 240V
180Vac - 280Vac
50Hz,60Hz;±5Hz
1
0.9leading…
0.9lagging
<3%
Single phase
4600W
4600VA *
20A
23A **
220V / 230V / 240V
180Vac - 280Vac
50Hz,60Hz;±5Hz
1
0.9leading…
0.9lagging
<3%
Single phase
CHPI 3.6KTL-M2 CHPI 4.2KTL-M2 CHPI 5KTL-M2
Input Data
DC reverse polarity protection
AC short-circuit protection
Ground fault monitoring
Grid monitoring
Integrated all-pole sensitive
leakage current monitoring unit
Max . efficiency
Euro-eta
MPPT efficiency
yes
yes
yes
yes
yes
97.1%
96.5%
99.5%
yes
yes
yes
yes
yes
97.1%
96.5%
99.5%
yes
yes
yes
yes
yes
97.1%
96.5%
99.5%
Protection Devices
Efficiency