background image

   
 

 

14   

     

 

 

CHSM72M-HC 

CHSM72P-HC 

CHSM72M/LV-HC 

CHSM72M(BL)-HC 

2018*1002*40 

2018*1002*35 

+5400Pa 

-2400Pa 

+2400Pa 

-2400Pa 

+5400/-2400Pa 

Installation scope 

350±50mm 

--- 

+2400Pa 

-2400Pa 

+Bumper 

2108*1048*35 

2094*1038*35 

+5400Pa 

-2400Pa 

+2400Pa 

-2400Pa 

+5400/-2400Pa 

Installation scope 

400±50mm 

--- 

+2400Pa 

-2400Pa 

+Bumper 

2256*1133*35 

2279*1134*35 

2278*1134*35 

+5400Pa 

-2400Pa 

+2400Pa 

-2400Pa 

+5400/-2400Pa 

Installation scope 

400~450mm 

--- 

+1800Pa 

-1800Pa 

+Bumper 

CHSM66M-HC 

CHSM66M(BL)-HC 

2384*1303*35 

+5400Pa 

-2400Pa 

+2400Pa 

-2400Pa 

+5400/-2400Pa 

Installation scope 

475~525mm 

--- 

+1800Pa 

-1800Pa 

+Bumper 

6

 

Electrical Installation 

6.1

 

Electrical characteristics

 

The  electrical  characteristics  are  detailed  in  the  PV 

module product manual. 

The rated values of electrical characteristics, including 

I

sc

,  V

oc

  and  P

mpp

,  have  some  tolerance  with  the 

measured  values  at  standard  condition:  ±5%  for  I

sc

±3%  for  V

oc

  and  ±3%  for  P

mpp

.  The  standard  test 

condition  refers  to  1000W/m

2

,  AM1.5  and  cell 

temperature at 25℃. 

According  to  IEC  and  UL  standards,  the  standard 

maximum system voltage for the regular module series 

is  1000V,  the  1500V  standard  products  are  also 

available  according  to  the  requirements.  The  IEC  & 

UL  standard  maximum  system  voltage  for  half-cell 

module series is 1500V (except for BL &LV series PV 

modules). 

The  actual  maximum  voltage  must  be  less  than  the 

standard  maximum  system  voltage  and  the  maximum 

output  voltage  of  the  inverter  and  other  electrical 

equipment  installed  in  the  system.  The  number  of PV 

modules connected in series  should match the voltage 

specification  of  the  inverter.  The  total  voltage 

generated  by  PV  modules  in  series  should  not  be 

higher  than  the  maximum  voltage  allowed  by  the 

system. 

To  ensure  the  above  requirements,  the  open-circuit 

voltage  of  the  string  needs  to  be  calculated  at  the 

lowest  expected  ambient  temperature  at  certain 

location.  This  can  be  calculated  using  the  following 

formula: 

Maximum system voltage≥N*

V

oc

*[1+

TC

voc

*(T

min

-25)] 

Where:   

N: number of PV modules in a single string 

V

oc

:  open-circuit  voltage  of each PV  module  (refer  to 

the PV module nameplate or product manual) 

TC

voc

:  temperature  coefficient  of  PV  module  for 

open-circuit  voltage  (refer  to  the  PV  module  product 

manual) 

T

min

: minimum ambient temperature. 

ATTENTION

 

Summary of Contents for CHSM54M(BL)-HC

Page 1: ...1 Crystalline Silicon PV Module Installation Manual...

Page 2: ...1 Transport 6 4 2 Unpack 7 4 3 Stack 7 5 Mechanical installation 7 5 1 Environment 7 5 2 Tilt angle selection 8 5 3 Mounting Guide 8 5 3 1 Bolted mounting 9 5 3 2 Clamped mounting 10 6 Electrical Inst...

Page 3: ...ed with is beyond the control of Chint Solar Chint shall not be liable for any form of loss including but not limited to loss damage casualty or additional cost caused by improper installation operati...

Page 4: ...a or PV module storage area It is forbidden to install or use damaged PV modules It is forbidden to repair PV modules by unauthorized personnel including but not limited to replacing any part of PV mo...

Page 5: ...and be aware of bumps in the corners When installing or repairing the PV system do not wear any metal accessories to avoid the risk of electric shock if it is installed far above the ground please we...

Page 6: ...connector or make electrical connections in any other way 4 Handling and unpacking If the PV module is not in use please do not open the product packaging The goods should be stored in a dark dry and...

Page 7: ...from colliding and scratching with the cement surface hard object on the ground color steel tile metal corrugated etc When the PV modules are stacked they must be neatly and stably stacked on a horiz...

Page 8: ...tion The tilt angle of a PV module refers to the angle between the surface of the PV module and the ground surface as shown in Fig 1 The power output of a PV module is maximized when it faces the sun...

Page 9: ...raction effect therefore the space between two adjacent PV module frames should be no less than 10mm when mounted For detailed installation methods please refer to the following specifications 5 3 1 B...

Page 10: ...e installed across the support frame Fig 8 or parallel to the frame of the photovoltaic module Fig 9 When using clamps to install each module must be secured with a minimum of 4 clamps Fig 8 Rails ove...

Page 11: ...shown in Fig 10 and the fringe clamp shown in Fig 11 and Fig 12 The mid clamp has dimensions of a 40 mm b 26 mm c 5 mm d 28 mm 9 mm For module of 182mm wafer the size of mid and fringe clamp must mee...

Page 12: ...00Pa 2400Pa 5400 2400Pa Installation scope 198 408mm 2400 2400Pa Installation scope 50 200mm CHSM60M HC CHSM60P HC CHSM60M BL HC CHSM60M LV HC 1666 992 35 5400Pa 2400Pa 5400 2400Pa Installation scope...

Page 13: ...M HC CHSM54M BL HC CHSM54M LV HC 1708 1133 30 1708 1133 35 1722 1134 30 1722 1134 35 5400Pa 2400Pa 5400 2400Pa Installation scope 359 50mm 1400 1400Pa Installation scope 200 50mm CHSM6612M CHSM6612M H...

Page 14: ...m voltage for the regular module series is 1000V the 1500V standard products are also available according to the requirements The IEC UL standard maximum system voltage for half cell module series is...

Page 15: ...ge ratings conductor capacities fuse ratings and control sizes for PV output Depending on the maximum rated fuse current of the PV module and the local electrical installation standards the connection...

Page 16: ...ng connectors to direct sunlight and soaking in water Avoid the connectors falling on the ground or the roof Do not plug or unplug the connectors when the PV module is in live state When it is necessa...

Page 17: ...that meet the requirements of UL 467 and is suitable for electrical bonding and grounding of PV modules Other grounding methods may be used when the racking system is tested following the UL 2703 req...

Page 18: ...it is generally not necessary to clean the PV module as the rainfall will provide a self cleaning effect If there is a large accumulation of dirt on the PV module surface that has seriously affected t...

Page 19: ...released in June 2018 Rev 1 1 released in July 2020 Rev 1 2 released in October 2021 CHINT SOLAR ZHEJIANG Co Ltd Add 1335 Bin an Rd Binjiang District Hangzhou China 310053 Tel 86 571 5603 1888 Fax 86...

Reviews: