background image

   
 

 

15   

     

 

 

 

Under  normal  operating  conditions,  the  output 

current  and/or  voltage  of  the  PV  module  may  be 

higher  than  the  value  under  standard  testing 

conditions.  Therefore,  in  PV  system  design,  for 

example  determining  the  rated  voltage  of 

equipment,  current  carrying  capacity  of  wires  and 

fuse  and  parameters  associated  with  the  output 

power  of  PV  modules,  the  corresponding 

short-circuit  current  and  open-circuit  voltage 

should be applied with a safety factor of 1.25. The 

number  of  PV  modules  connected  in  series  should 

match the voltage specification of the inverter. The 

total  voltage  generated  by  the  PV  modules 

connected  in  series  cannot  be  higher  than  the 

maximum voltage allowed by the system. 

 

According  to  the  National  Electrical  Code  690.8, 

the  parameters  need  to  be  multiplied  by  an 

additional  125%  (80%  derating)  factor,  i.e.  the 

parameters  including  the  optimum  operating 

current and voltage at standard test condition (STC) 

needs to be multiplied by the square of 1.25 when 

determining  voltage  ratings,  conductor  capacities, 

fuse ratings, and control sizes for PV output. 

 

Depending  on  the  maximum  rated  fuse  current  of 

the  PV  module  and  the  local  electrical  installation 

standards,  the  connection  of  parallel  strings  of  PV 

modules  needs  to  be  equipped  with  suitable  fuses 

or preventive diodes for circuit protection purposes. 

6.2

 

Electrical connection 

To  ensure  the  normal  operation  of  the  system,  make 

sure  the  polarity  of  cables  is  correct  when  connecting 

modules or loads, such as inverters and batteries. If the 

PV  module  is  not  connected  correctly,  the  bypass 

diode  may  be  damaged.  Fig.  14  shows  how  the  PV 

modules  are  connected  in  series  and  parallel.  PV 

modules  can  be  wired  in  series  to  boost  the  voltage. 

Series  connections  are  made  by  connecting  the  wire 

from  the  positive  terminal  of  one  module  to  the 

negative terminal of the next module. PV modules can 

be  wired  in  parallel  to  increase  the  current  by 

connecting  the positive terminal of one module to the 

positive terminal of the next module. If a module is not 

connected  correctly,  the  bypass  diode  may  be 

damaged. 

 

 

 

Fig. 14 Schematic diagram of electrical connection 

ATTENTION 

 

If one PV module string (or PV array) is connected 

Summary of Contents for CHSM54M(BL)-HC

Page 1: ...1 Crystalline Silicon PV Module Installation Manual...

Page 2: ...1 Transport 6 4 2 Unpack 7 4 3 Stack 7 5 Mechanical installation 7 5 1 Environment 7 5 2 Tilt angle selection 8 5 3 Mounting Guide 8 5 3 1 Bolted mounting 9 5 3 2 Clamped mounting 10 6 Electrical Inst...

Page 3: ...ed with is beyond the control of Chint Solar Chint shall not be liable for any form of loss including but not limited to loss damage casualty or additional cost caused by improper installation operati...

Page 4: ...a or PV module storage area It is forbidden to install or use damaged PV modules It is forbidden to repair PV modules by unauthorized personnel including but not limited to replacing any part of PV mo...

Page 5: ...and be aware of bumps in the corners When installing or repairing the PV system do not wear any metal accessories to avoid the risk of electric shock if it is installed far above the ground please we...

Page 6: ...connector or make electrical connections in any other way 4 Handling and unpacking If the PV module is not in use please do not open the product packaging The goods should be stored in a dark dry and...

Page 7: ...from colliding and scratching with the cement surface hard object on the ground color steel tile metal corrugated etc When the PV modules are stacked they must be neatly and stably stacked on a horiz...

Page 8: ...tion The tilt angle of a PV module refers to the angle between the surface of the PV module and the ground surface as shown in Fig 1 The power output of a PV module is maximized when it faces the sun...

Page 9: ...raction effect therefore the space between two adjacent PV module frames should be no less than 10mm when mounted For detailed installation methods please refer to the following specifications 5 3 1 B...

Page 10: ...e installed across the support frame Fig 8 or parallel to the frame of the photovoltaic module Fig 9 When using clamps to install each module must be secured with a minimum of 4 clamps Fig 8 Rails ove...

Page 11: ...shown in Fig 10 and the fringe clamp shown in Fig 11 and Fig 12 The mid clamp has dimensions of a 40 mm b 26 mm c 5 mm d 28 mm 9 mm For module of 182mm wafer the size of mid and fringe clamp must mee...

Page 12: ...00Pa 2400Pa 5400 2400Pa Installation scope 198 408mm 2400 2400Pa Installation scope 50 200mm CHSM60M HC CHSM60P HC CHSM60M BL HC CHSM60M LV HC 1666 992 35 5400Pa 2400Pa 5400 2400Pa Installation scope...

Page 13: ...M HC CHSM54M BL HC CHSM54M LV HC 1708 1133 30 1708 1133 35 1722 1134 30 1722 1134 35 5400Pa 2400Pa 5400 2400Pa Installation scope 359 50mm 1400 1400Pa Installation scope 200 50mm CHSM6612M CHSM6612M H...

Page 14: ...m voltage for the regular module series is 1000V the 1500V standard products are also available according to the requirements The IEC UL standard maximum system voltage for half cell module series is...

Page 15: ...ge ratings conductor capacities fuse ratings and control sizes for PV output Depending on the maximum rated fuse current of the PV module and the local electrical installation standards the connection...

Page 16: ...ng connectors to direct sunlight and soaking in water Avoid the connectors falling on the ground or the roof Do not plug or unplug the connectors when the PV module is in live state When it is necessa...

Page 17: ...that meet the requirements of UL 467 and is suitable for electrical bonding and grounding of PV modules Other grounding methods may be used when the racking system is tested following the UL 2703 req...

Page 18: ...it is generally not necessary to clean the PV module as the rainfall will provide a self cleaning effect If there is a large accumulation of dirt on the PV module surface that has seriously affected t...

Page 19: ...released in June 2018 Rev 1 1 released in July 2020 Rev 1 2 released in October 2021 CHINT SOLAR ZHEJIANG Co Ltd Add 1335 Bin an Rd Binjiang District Hangzhou China 310053 Tel 86 571 5603 1888 Fax 86...

Reviews: