background image

 

 

Chint Solar (Zhejiang) Co., Ltd. | Add:1335 Bin´an Road, Binjiang District, Hangzhou | P.C: 310053 
Tel: 0086-571-5603 1888 | Fax: 086-571-5603 2316 | Website: http://energy.chint.com/

 

and facing south in the northern hemisphere. 

3.1.5  To maintain the modules’ Class C fire rating, the fire class of the roof and building 

materials should be higher than Class C. 

3.1.6  To maintain the modules’ fire performance type 1(for US market), it could be possible to 

achieve the Class A system fire rating, with the Class A class racking system. 

3.2  Installation Methods 

3.2.1 Bolting through the mounting holes 

All  modules  (excluding  the  double  glass  module)  must  be  securely  fastened  with  at  least  4 

bolts (Figure a and Figure b). For maximum security against strong winds or heavy snow falls, all of 
the mounting holes are recommended to be used.   

 

 
 
 
 
 
 
 

Fig a   

 

 

 

 

 

 

 

Fig b 

 
Remark:  As for  above  diagram,  the  solid  red  arrows  indicate  primary  bolt  positions;  dashed 

blue arrows indicate positions where bolts can be added for additional support. 

Bolts are inserted as described in the process below (Sketch figure c). 

a)  Place the module on the supporting bars underneath. 
b)  Insert the four stainless-steel bolts (M6) through the holes (7x11.5mm) or stainless-steel 

bolts (M8) through the holes (9x14mm) in the frame according to the Figure a & Figure b. 
For maximum security against strong winds and heavy snow, all available mounting holes 
should be used. 

c)  Secure each bolt to the frame with stainless-steel washers, one for each side of the 

mounting structure; and screw on either a stainless-steel spring washer or a toothed lock 
washer. Finally, secure with a stainless steel nut. 

d)  The reference value of tightening torques should be within 9~12Nm& 17~23 Nm 

respectively for M6 &M8 bolts, depending on bolt class. For the bolt grade, the technical 
guideline from the fastener suppliers should be followed. 
For the torque value, recommendations from specific clamping hardware suppliers should 
prevail. 
 

Summary of Contents for CHSM60M-HC

Page 1: ...int com Crystalline Silicon PV Module Installation Manual 1 Introduction 1 1 Purpose 1 2 Limitation of Liability 1 3 Precautions for Installation 2 Safety 2 1 General Safety 2 2 Installation Safety 3 Mechanical Installation 3 1 Installation Condition 3 2 Installation Methods 4 Electrical Installation 4 1 Installation Condition 4 2 Grounding 5 Maintenance ...

Page 2: ...the responsibility and expressly disclaims liability for loss damage or expense arising out of or in any way connected with such installation operation use or maintenance Chint Solar reserves the right to change the manual without prior notice 1 3 Precautions of Installation 1 3 1 Module s unpack and transfer a When the whole pallet of modules are delivered to the site and unloaded make sure the s...

Page 3: ...ardboard bedding need to be underside the modules If the modules will be installed on the rooftop the number of each stack is suggested no more than 20 In case of the poor load bearing capacity it s recommended that the designer and or installer check with the structural engineer or architect to determine the amount of load allowable for specific location During the whole process the installation ...

Page 4: ...or panels 2 1 9 Do not attempt to disassemble the modules and do not remove any attached components from the modules 2 1 10 Do not scratch or hit at the back sheet the glass the terminal box Do not pull the cables or touch them with bare hands 2 1 11 Do not drill holes in the frame or scratch the insulating coating of the frame 2 1 12 Keep the PV module packed in the carton until installation 2 1 ...

Page 5: ...e than two strings are connected in parallel 2 2 16 A certain gap is maintained between the PV module and the mounting surface to prevent the mounting surface touching the junction box 2 2 17 Standing on the solar PV module is forbidden and also prohibit installation tools or other objects hitting surface of the solar PV module 2 2 18 The solar modules are recommended to be installed over a firepr...

Page 6: ... arrows indicate primary bolt positions dashed blue arrows indicate positions where bolts can be added for additional support Bolts are inserted as described in the process below Sketch figure c a Place the module on the supporting bars underneath b Insert the four stainless steel bolts M6 through the holes 7x11 5mm or stainless steel bolts M8 through the holes 9x14mm in the frame according to the...

Page 7: ... must please confirm with our product team to get approval an Road Binjiang District Hangzhou P C 310053 5603 2316 Website http energy chint com Fig c on the frame surface Modules can be laid either across the supporting bars Figure d f Fig g The length of supporting bars must be longer than the length of module frame otherwise please confirm with our product team to get approval or parallel to th...

Page 8: ... 3 2mm glass 1954 990 40 1960 992 40 489 299 4 0mm glass CHSM72M HC CHSM72P HC 1986 992 40 2018 1002 40 505 315 3 2mm glass 2000 992 40 510 315 3 2mm glass To fasten the module a Place the module on the two supporting bars not provided The bars should be made with stainless material and treated with an anti corrosion process e g anodic oxidation treatment or aluminum profile Each solar PV module n...

Page 9: ... modules must be supported along the length of the edge and should overlap the array rail by 10mm 14mm Figure j g Especially for Figure f Figure g mounting method the recommended mechanical load on panels is less than 2400Pa and this method is only suitable for 45mm frame module series Figure k 4 Electrical Installation 4 1Installation Condition 4 1 1 The electrical characteristics are within 10 o...

Page 10: ...eported at standard test conditions Accordingly the value of Isc marked on this module should be multiplied by a factor of 1 25 when determining component conductor ampacities fuse sizes and size of controls connected to the PV output 4 1 5 Refer to Section 690 8 of the National Electrical Code for an additional multiplying factor of 125 80 derating which may be applicable 4 1 6 Each module or ser...

Page 11: ...ire around the bolt Note that the copper wire cannot be attached directly to the aluminum 4 2 4 Put the bolt through the cut washer and then through the hole in the aluminum frame 4 2 5 Add the spring washer and nut on the other side of the bolt and tighten to secure all parts The tightening torque should be 210 20 N cm 4 2 6 Approve the use of UL 467 certified bonding and grounding devices includ...

Page 12: ...weather pollution O M operator shall keep a record of weather condition everyday with data 5 5 Condition of Cleaning 5 5 1 Use clean water or filtered water with soft type material a sponge to wipe the PV module Never use chemicals on the surface of the module 5 5 2 Cleaning after sunset or before sunrise is recommended for safety of O M operator shock from heat stroke 5 5 3 Do not use abrasive po...

Reviews: