Operation Manual Touchscreen
6.1.1 SETPOINT HUMIDITY
In the "Humidity" setpoint menu, the desired relative humidity is entered as a percentage when the
active drying is stopped. If the setpoint exceeds 15 minutes, the device automatically performs a
regeneration.
If "0" is entered, the continuous operation of the drying unit is activated. The maximum residual
moisture is achieved by maximum energy consumption. If the fixed value of 0.5% RH is exceeded
more than 15 minutes, the device automatically performs a regeneration.
In order to avoid overloading the drying unit, there is a break between two automatic regenerations of
3 hours. This pause can only be skipped by initiating a manual regeneration (see 6.4).
No active humidification is installed in the cabinet. As a result, a longer time can be passed before this
is reached when the change from low humidity to a higher setpoint occurs. By deliberately opening
the door, this process can be accelerated.
6.1.2 HUMIDITY ALARM LIMIT
This is where the humidity alarm threshold is set, when the acoustic and the optional optical alarm are
activated.
6.1.2.1 ALARM
The alarm activates an acoustic signal and turns on the red background light in the text display. The
red flashing light is activated when the optional alarm light is used. The acoustic alarm can be
acknowledged by pressing the [Alarm] button, followed up with [Quit Alarm]. This is then active again
when the alarm is re-activated. The alarm message in the display and the traffic light message are
automatically ended after elimination of the alarm cause.
6.1.3 HUMIDITY ALARM DELAY
To ensure that every short-term increase in the humidity does not trigger an alarm, the alarm delay
for the humidity is set with this value.
6.1.4 SETPOINT TEMPERATURE
The menu items 6.1.4 to 6.1.6 are only visible if an optional heating / cooling system has been
installed. You can select the required temperature for the cabinet in this menu.
If the selected setpoint is below the temperature limit / ambient temperature, the heating remains
inactive. This also applies to an optional cooling system.
6.1.5 TEMPERATURE DEVIATION
The deviation (difference) to the temperature setpoint is defined here, and the acoustic and the
optional optical alarm are activated when the signal is exceeded (see 6.1.2.1).
6.1.6 TEMPERATURE ALARM DELAY
In order to prevent an alarm from being triggered by every short-term drop or increase in
temperature, the alarm delay for the temperature drop out is set with this value.
Please note that heating is deactivated during regeneration. This can lead to a short-term drop
(maximum 20 minutes) of the cut-off temperature.
6.1.7 DIAGNOSE
On the first page is access to the diagnosis of the display. You can also find the status overview of the
LOGO! logic module.