Installation
&
Servicing
instructions
AT
AG
A200SOV
15
We suggest you design a simple flue gas system and air supply system using table 6.
For further information about the available components of the flue gas and air supply
system we recommend you consult the Monopass Flue system literature.
The ATAG flue gas system is meant and designed solely for the use on ATAG central
heating boilers adjusted to Nat gas or LPG. The maximum flue gas temperatures are
below 70°C (full load 80/60°C)
The proper operation can be influenced harmfully by changes of or adjustments to the
correct set up.
Possible warranty claims will not be honoured if incorrect changes result in non compliance
with the installation manual or local rules and regulations.
The flue gas systems described in this document are solely suited for ATAG central
heating boilers of the ATAG boiler range. For this purpose the CE Certificate has been
supplemented under the Gastec nr: 0063BR3405, 0063BQ3021, 0063AS3538 and
0063AU3110.
The flue gas system should be built up using only ATAG program products. Combination
with other brands or systems without written permission from ATAG Heating is not
permitted.
The terminal should be located where dispersal of combustion products is not unimpeded
and with due regard for the damage or discolouration that might occur to parts of the
building in the vicinity (see fig 7).
terminal position for fan assisted boiler
minimum
distance
A directly below an open window or other opening
(e.g. air brick)
mm
300
B below gutters, soil pipes or drain pipes
mm
75
C below eaves
mm
200
D below balconies or car port roof
mm
200
E from vertical drain pipes and soil pipes
mm
75
F from internal or external corners
mm
300
G above ground or below balcony level
mm
300
H from a surface facing a terminal
mm
600
I from a terminal facing a terminal
mm
1200
J from an opening in the car port (e.g. door
window) into dwelling
mm
1200
K vertically from a terminal on the same wall
mm
1500
L horizontally from a terminal on the same wall
mm
300
M horizontally from a vertical terminal to a wall
mm
300
Dimensions
table 6
figure 7